Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 117
Additional information Description
This setting does not affect the failsafe mode of other outputs and totalizers. This is
specified in separate parameters.
"Min." option
The current output adopts the value of the lower level for signal on alarm.
The signal on alarm level is defined via the Current span parameter (→  106).
"Max." option
The current output adopts the value of the upper level for signal on alarm.
The signal on alarm level is defined via the Current span parameter (→  106).
"Last valid value" option
The current output adopts the last measured value that was valid before the device alarm
occurred.
"Actual value" option
The current output adopts the measured value on the basis of the current flow
measurement; the device alarm is ignored.
"Defined value" option
The current output adopts a defined measured value.
The measured value is defined via the Failure current parameter (→  117).
Failure current
Navigation  Expert → Output → Curr.output 1 to n → Failure current (0352–1 to n)
Prerequisite The Defined value option is selected in the Failure mode parameter (→  116).
Description Use this function to enter a fixed value that the current output adopts in the event of a
device alarm.
User entry 0 to 22.5 mA
Factory setting 22.5 mA
Output curr. 1 to n
Navigation  Expert → Output → Curr.output 1 to n → Output curr. 1 to n (0361–1 to n)
Description Displays the current value currently calculated for the current output.
User interface 3.59 to 22.5 mA