Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 195
Factory setting Overwriting
Additional information Selection
Overwriting
The device memory applies the FIFO principle.
Not overwriting
Data logging is canceled if the measured value memory is full (single shot).
Logging delay
Navigation  Expert → Diagnostics → Data logging → Logging delay (0859)
Prerequisite In the Data logging parameter (→  194), the Not overwriting option is selected.
Description Use this function to enter the time delay for measured value logging.
User entry 0 to 999 h
Factory setting 0 h
Additional information Description
Once measured value logging has been started with the Data log.control parameter
(→  195), the device does not save any data for the duration of the time delay entered.
Data log.control
Navigation  Expert → Diagnostics → Data logging → Data log.control (0857)
Prerequisite In the Data logging parameter (→  194), the Not overwriting option is selected.
Description Use this function to start and stop measured value logging.
Selection None
Delete + start
Stop
Factory setting None
Additional information Selection
None
Initial measured value logging status.
Delete + start
All the measured values recorded for all the channels are deleted and measured value
logging starts again.
Stop
Measured value logging is stopped.