Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 121
A0026883
6 Quantity-proportional pulse (pulse value) with pulse width to be configured
B Pulse width entered
P Pauses between the individual pulses
"Frequency" option
Flow-proportional frequency output with 1:1 on/off ratio
An output frequency is output that is proportional to the value of a process variable, such
as volume flow, mass flow, corrected volume flow, flow velocity, conductivity, corrected
conductivity, temperature or electronic temperature.
Example
• Flow rate approx. 100 g/s
• Max. frequency 10 kHz
• Flow rate at max. frequency 1 000 g/s
• Output frequency approx. 1 000 Hz
A0026886
7 Flow-proportional frequency output
"Switch" option
Contact for displaying a condition (e.g. alarm or warning if a limit value is reached)
Example
Alarm response without alarm
A0026884
8 No alarm, high level
Example
Alarm response in case of alarm