3.5 Liquid-Cooled Add-In Card Installation (D50DNP1MHCPLC and
D50DNP1MFALLC Modules)
1U liquid-cooled module can accommodate up to two low-profile liquid-cooled PCIe* add-in cards. These
models are supported:
NVIDIA* MCX653105A-HDAL
NVIDIA* MCX653106A-HDAL
NVIDIA* MCX75310AAS-HEAL
NVIDIA* MCX75310AAS-NEAL
Required Tools and Supplies
Liquid-cooled PCIe* add-in card kit
Anti-static wrist strap and conductive workbench pad (recommended)
Phillips* head screwdriver #1
Note: The following steps to install PCIe* add-in card should be performed along with the instructions for
the add-in card.
1. Prepare the PCIe* add-in card by attaching the thermal pad to the ASIC or heat spreader as instructed
in the card documentation.
2. Remove the riser assembly following procedure described in Section 3.4.1 or Section 3.4.2. Pay
attention not to damage or displace the thermal strips attached to the conduction plate.
3. Install PCIe* add-in card following the procedure described in Section 3.4.3 (see letter B)
4. Install the riser assembly into the module following the procedure described in Section 3.4.6.
5. Secure the PCIe add-in card to the conduction plate with three screws supplied with the card. Tighten
to 5 in-lb.