Chapter 5 Memory and Parameter
5-35
② Current speed filter time constant = 50 ms
③ Current speed filter time constant = 100 ms
9) Error reset monitoring time
Set the monitoring time in the event of error reset occurred in the servo drive. (unit: ms) If the error which occurred in the
servo drive within the error reset monitoring time, error reset monitoring is terminated and error reset time out error of servo
drive (error code: 0x1070) is occurred.
10) S/W limit during speed control
When software limit is detected during the operation at fixed speed by speed control, this is used to stop the motor.
Operations according to the set values are as follows.
- ‘0: Don’t detect’
If it is under the speed control even when the software limit function is activated, software limit is not detected.
- ‘1: Detect’
If it is under the speed control even when the software limit function is activated, software limit is detected.