Standards Compliance
5
5.3 UL Standards
SIEPCYEUOQ2V01A Q2V Technical Manual 171
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
Single-Phase 200 V Class (UL Compliance)
Model Terminal
Recommended
Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening Torque
N∙m (in∙lb)
Size Shape
B001
L/L1, N/L2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
14
*2
14
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)
B002
L/L1, N/L2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
14
*2
14
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)
B004
L/L1, N/L2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
14
*2
14
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)
B006
L/L1, N/L2 12 14 - 10 8 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 14 14 - 12 8 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1 12 14 - 10 8 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 14 14 - 12 8 M3
0.5 - 0.6
(4.4 - 5.3)
10
*2
14 - 10
*2
- M4
1.2 - 1.5
(10.6 - 13.3)
B010
L/L1, N/L2 10 12 - 10 8 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 14 14 - 12 8 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1 10 12 - 10 8 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 14 14 - 12 8 M3
0.5 - 0.6
(4.4 - 5.3)
10
*2
14 - 10
*2
- M4
1.2 - 1.5
(10.6 - 13.3)