Parameter Details
12
12.9 n: SPECIAL
SIEPCYEUOQ2V01A Q2V Technical Manual 681
Figure 12.130 Configure Feed Forward Control
Before You Use Feed Forward Control
Do one of these procedures before you use feed forward control.
Run Auto-Tuning to set motor parameters.
When you cannot do Auto-Tuning, manually set motor parameters with the information on the motor nameplate
or test reports. Set E2: MOTOR 1 PARAMETERS for induction motors. Set E5: PM MOTOR SETTINGS for PM
motors.
Set C5: ASR - SPEED REGULATION individually to adjust the speed control loop (ASR).
If you can connect a motor to a machine and rotate it during Auto-Tuning, do Inertia Tuning.
The drive automatically adjusts feed forward parameters during Inertia Tuning.
If you cannot do Inertia Tuning, refer to Figure 12.130 and set the parameters related to feed forward control
individually.
n5-01: FF Control Selection
No.
(Hex.)
Name Description
Default
(Range)
n5-01
(05B0)
n5: FF Control Selection
Sets the feed forward function.
0
(0, 1)
0 : Disabled
1 : Enabled
n5-02: Mot Inertia Acceleration Time
No.
(Hex.)
Name Description
Default
(Range)
n5-02
(05B1)
Mot Inertia Acceleration
Time
Sets the length of time for the motor to accelerate from the stopped to the maximum frequency
with a single motor at the rated torque. Inertia Tuning automatically sets the motor acceleration
time.
Determined by C6-01, E5-
01, and o2-04
(0.001 - 10.000 s)
If you cannot do Inertia Tuning, calculate the motor acceleration time as shown here or measure the motor
acceleration time and set n5-02 to this value.
Calculate the Motor Acceleration Time
Use this formula to find the motor acceleration time:
J
Motor
= Moment of inertia of motor (kg m
2
)
n
rated
= Motor rated speed (min
-1
, r/min)
T
rated
= Motor rated torque (N m)
You can also use this formula to find the motor acceleration time:
f
rated
= Motor rated frequency (Hz)
P = Number of motor poles