2 Design
2 - 78
High-function General-purpose Inverter RX2 Series User’s Manual
Integral
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code and any additional local
codes.
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the Canadian Electrical Code, part1 or the equiva-
lent. (For Canada)
Field Wiring Terminal Conductor Size and Torque Values Making for
Field Wiring Terminal
Model
3G3RX2
Load
Type
Required
Torque
(N·m)
Conductor size
(AWG)
Model
3G3RX2
Load
Type
Required
Torque
(N·m)
Conductor size
(AWG)
A2004
VLD
1.4 14LD
ND
A2007
VLD
1.4 14 A4007
VLD
1.4 14LD LD
ND ND
A2015
VLD
1.4 14 A4015
VLD
1.4 14LD LD
ND ND
A2022
VLD
1.4 10 A4022
VLD
1.4 14LD LD
ND ND
A2037
VLD
1.4 10 A4037
VLD
1.4
12
LD LD
14
ND ND
A2055
VLD
3 8 A4055
VLD
3
10
LD LD
12
ND ND
A2075
VLD
3
6
A4075
VLD
3
8
LD
8
LD
10
ND ND
A2110
VLD
4
4
A4110
VLD
48LD LD
ND 6 ND
A2150
VLD
2.5 to 3.0
3
A4150
VLD
48LD LD
ND 4 ND
A2185
VLD
2.5 to 3.0
1
A4185
VLD
4
6
LD 2 LD
ND 3 ND 8
A2220
VLD
5.5 to 6.6
2/0
A4220
VLD
4
4
LD 1/0 LD
ND 1 ND 6
A2300
VLD
6
Parallel of 1/0
A4300
VLD
6
1
LD
LD 2
ND 2/0 ND 3
A2370
VLD
6 to 10
Parallel of 1/0
A4370
VLD
15 1LD Parallel of 1/0 LD
ND 15 4/0 ND