2 - 79
2 Design
High-function General-purpose Inverter RX2 Series User’s Manual
2-3 Wiring
2
2-3-11 Compatibility Conditions of UL/CSA Standards
Note 1. Temperature rating of field wiring installed conductors is 75°C only.
2. Use Copper conductors only.
200V class
A2450
VLD
6 to 10
Parallel of 2/0
A4450
VLD
15
1/0
LD Parallel of 1/0 LD
ND Parallel of 1/0 ND 1
A2550
VLD
10 to 12
Parallel of 3/0
A4550
VLD 6 to 10 Parallel of 1/0
LD Parallel of 3/0 LD
15
2/0
ND 350kcmil ND 1/0
B4750
VLD
10 to 12 Parallel of 1/0LD
ND
B4900
VLD
10 to 12
Parallel of 2/0
LD
Parallel of 1/0
ND
B411K
VLD
10 to 12
Parallel of 3/0
LD
Parallel of 2/0
ND
B413K
VLD
10 to 12
P. of 250kxmil
LD Parallel of 4/0
ND Parallel of 3/0
Required Protection by Fuse and Circuit-breakers
Model
3G3RX2
Fuse Circuit Breaker
Type
Maximum Rating Maximum Rating
Voltage (V) Current (A) Voltage (V) Current (A)
A2004 Class J or T 600 15 - -
A2007 Class J or T 600 30 - -
A2015 Class J or T 600 40 - -
A2022 Class J or T 600 40 - -
A2037 Class J or T 600 50 - -
A2055 Class J or T 600 100 - -
A2075 Class J or T 600 150 - -
A2110 Class J or T 600 150 - -
A2150 Class J or T 600 150 - -
A2185 Class J or T 600 200 - -
A2220 Class J or T 600 200 - -
A2300 Class J or T 600 300 - -
A2370 Class J or T 600 300 - -
A2450 Class J or T 600 400 - -
A2550 Class J or T 600 500 - -
Model
3G3RX2
Load
Type
Required
Torque
(N·m)
Conductor size
(AWG)
Model
3G3RX2
Load
Type
Required
Torque
(N·m)
Conductor size
(AWG)