6 Basic Parameter Settings
6 - 6
High-function General-purpose Inverter RX2 Series User’s Manual
Parameters
Parameters Chosen for Initialization [Ub-01]
Item
Parameters
Data Description
Default
data
Initialize
Mode
selection
[Ub-01]
00 The initialization is disabled.
00
01 The trip history and retry history are cleared.
02 Parameters all initialized
03
The trip history, retry history, and all parameters are initial-
ized.
04
The trip history, retry history, all parameters, and program
data for EzSQ are initialized.
05
Parameters other than those of I/O terminal function are
initialized.
06
Parameters other than the communication function param-
eters are initialized.
07
Parameters other than those of I/O terminal function and
communication function are initialized.
08
Only the program data for DriveProgramming are initial-
ized.
Initialize
Data
selection
[Ub-02]
00 Mode 0
01
01 Mode 1 (Factory setting)
02 Mode 2
03 Mode 3
Initialize
Enable
[Ub-05]
00 Function disabled
00
01 Initialization start
Item Parameter range Description
Classification of I/O terminal func-
tions
[CA-01] to [CA-11] Input terminal selection
[CA-21] to [CA-31] a/b contact selection
[CA-41] to [CA-51] Input terminal response
[Cb-40] Thermistor selection
[CC-01] to [CC-07] Output terminal selection
[CC-11] to [CC-17] a/b contact selection
[CC-20] to [CC-33] Output delay
[CC-40] to [CC-60] Logical operation function
Classification of communication
functions
[CF-01] to [CF-10] Setting of RS485 communication
[CF-20] to [CF-38] Setting of EzCOM communication