6 Basic Parameter Settings
6 - 68
High-function General-purpose Inverter RX2 Series User’s Manual
Select a pattern for each of the acceleration and the deceleration patterns by referring to the following
table.
Determine the bulging degree by referring to the following figure.
Pattern Selection
Set value 00 01 02 03 04
Curve Linear S-shaped U-shaped
Inverse-U-
shaped
EL-S-shaped
[AC-03]
(Acceleration)
[AC-04]
(Deceleration)
Description
Providing a linear
acceleration up or
deceleration
down to the set
frequency value.
Effective in the
prevention of load
collapse in lifts or
on conveyors, for
example.
Effective when a winder or the like
needs to control of the tension and/or
prevent the object to be wound from
being cut. Usable for 1-shot wind-
ing/feeding.
Providing a
shockless
start/stop as in
the case of the
S-shaped curve,
but providing a
linear middle sec-
tor.
Curve Constant (Degree of Bulging) of Pattern
(100%)
96.9
82.4
17.6
3.1
25
50
75
10
02
10
02
.
68.4
64.6
65 .0
35.4
0.39
25 50 75
10
02
31.6
12.5
6.25
(100%) (100%)
35.0
Acceleration time until the set
value for the frequency is
reached (100%)
Output frequency (Hz)
Tar get
Frequency
Acceleration time until the set
value for the frequency is
reached (100%)
Output frequency (Hz)
Acceleration time until the set
value for the frequency is
reached (100%)
Time
Output frequency (Hz)
Time
Time
Tar get
Frequency
Target
Frequency