EasyManuals Logo

Omron RX2 Series User Manual

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #347 background imageLoading...
Page #347 background image
7 - 39
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-2 Selection of Motor Control Methods
7
7-2-16 Encoder Feedback Control
Precautions for Correct Use
When either [CA-82] or [ob-02] = 00, meaning that phase-A is leading, and when the opera-
tion is of forward rotation, the phase of the phase-A advances 90-degrees more than that of
the phase-B in a normal case.
When either [CA-82] or [ob-02] = 01, meaning that phase-B is leading, and when the opera-
tion is of forward rotation, the phase of the phase-B advances 90-degrees more than that of
the phase-A in a normal case.
To check if the encoder input into the main body or into PG option unit is correct, set [AA121]
= 00 to 03, meaning V/f control (00), and check the monitor for the [dA-08] frequency detec-
tion values. The wiring is correct if the forward operation [FW] has a positive (+) value and if
the reversal operation [RV] has a negative (-) value. If it is incorrect, either revising the wiring
or switching the Encoder position selection [CA-82] or [ob-02].
When the encoder and the motor shaft are connected to each other by means of a gear, for Tables (3)
and (4) conversion is made possible by setting up (3) Encoder gear-ratio’s numerator/(4) encoder
gear-ratio’s denominator.
Set the values ((3)/(4)) so as to be within a range between (1/50) to (20).
An exemplar case where a gear is attached there.
When the encoder’s rotating rate for the motor’s standard encoder becomes 1/10 for 1024 pulses,
Table (1) Encoder constant set-up: 1024 pulses
Table (3): Encoder’s gear ratio’s numerator: 1.
Table (4): Encoder’s gear ratio’s denominator: 10
Set up as above.
To acquire the frequency that was input through the encoder, the following settings are necessary.
Set-up of Tables (1), (3), and (4)
Set-up of the number of motor poles
Note When the selected control mode [AA121] is the induction motor control ([AA121] = 00 to 10), async.Motor
poles setting, 1st-motor [Hb103] is set as the number of motor poles.
Adjustment in Cases Where a Gear Exists between the Motor and
the Encoder
Encoder’s Speed Detection
Gear
(Load side/motor-side = 1/10)
Encoder
(1024pulse)
Motor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron RX2 Series and is the answer not in the manual?

Omron RX2 Series Specifications

General IconGeneral
BrandOmron
ModelRX2 Series
CategoryInverter
LanguageEnglish

Related product manuals