9 - 31
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-5 Modbus Communication Register Number List
9
9-5-2 Group d Register List
0439h 0438h Trip monitor 5 Factor
dE-15 R
1 to 255 1
043Ah 0439h
Trip monitor 5 Output fre-
quency
-59000 to 59000 0.01(Hz)
043Bh 043Ah (with sign)
043Ch 043Bh
Trip monitor 5 Output cur-
rent
0 to 65535 0.01(A)
043Dh 043Ch
Trip monitor 5 P-N DC volt-
age
0 to 10000 0.1(Vdc)
043Eh 043Dh Trip monitor 5 Inverter state
0 to 8
*5
1
043Fh 043Eh Trip monitor 5 LAD state
0 to 5
*5
1
0440h 043Fh
Trip monitor 5 INV control
mode
0 to 11
*5
1
0441h 0440h Trip monitor 5 Limit state
0 to 6
*5
1
0442h 0441h Trip monitor 5 Special state
0 to 6
*5
1
0444h 0443h Trip monitor 5 RUN time
0 to 1000000 1(hr)
0445h 0444h
0446h 0445h
Trip monitor 5 Power ON
time
0 to 1000000 1(hr)
0447h 0446h
0448h
Trip monitor 5 Absolute time
(year, month)
00 to 99 (BCD code)
01 to 12 (BCD code)
-
0449h 0448h
Trip monitor 5 Absolute time
(day, day of the week)
01 to 31 (BCD code)
00 to 06 (BCD code)
-
044Ah 0449h
Trip monitor 5 Absolute time
(hour, minute)
00 to 23 (BCD code)
00 to 59 (BCD code)
-
044Dh 044Ch Trip monitor 6 Factor
dE-16 R
1 to 255 1
044Eh 044Dh
Trip monitor 6 Output fre-
quency
-59000 to 59000 0.01(Hz)
044Fh 044Eh (with sign)
0450h 044Fh
Trip monitor 6 Output cur-
rent
0 to 65535 0.01(A)
0451h 0450h
Trip monitor 6 P-N DC volt-
age
0 to 10000 0.1(Vdc)
0452h 0451h Trip monitor 6 Inverter state
0 to 8
*5
1
0453h 0452h Trip monitor 6 LAD state
0 to 5
*5
1
0454h 0453h
Trip monitor 6 INV control
mode
0 to 11
*5
1
0455h 0454h Trip monitor 6 Limit state
0 to 6
*5
1
0456h 0455h Trip monitor 6 Special state
0 to 6
*5
1
0458h 0457h Trip monitor 6 RUN time
0 to 1000000 1(hr)
0459h 0458h
045Ah 0459h
Trip monitor 6 Power ON
time
0 to 1000000 1(hr)
045Bh 045Ah
045Ch 045Bh
Trip monitor 6 Absolute time
(year, month)
00 to 99 (BCD code)
01 to 12 (BCD code)
-
045Dh 045Ch
Trip monitor 6 Absolute time
(day, day of the week)
01 to 31 (BCD code)
00 to 06 (BCD code)
-
045Eh 045Dh
Trip monitor 6 Absolute time
(hour, minute)
00 to 23 (BCD code)
00 to 59 (BCD code)
-
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution