EasyManua.ls Logo

Omron RX2 Series - Page 624

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Communications Functions
9 - 32
High-function General-purpose Inverter RX2 Series User’s Manual
0461h 0460h Trip monitor 7 Factor
dE-17 R
1 to 255 1
0462h 0461h
Trip monitor 7 Output fre-
quency
-59000 to 59000 0.01(Hz)
0463h 0462h (with sign)
0464h 0463h
Trip monitor 7 Output cur-
rent
0 to 65535 0.01(A)
0465h 0464h
Trip monitor 7 P-N DC volt-
age
0 to 10000 0.1(Vdc)
0466h 0465h Trip monitor 7 Inverter state
0 to 8
*5
1
0467h 0466h Trip monitor 7 LAD state
0 to 5
*5
1
0468h 0467h
Trip monitor 7 INV control
mode
0 to 11
*5
1
0469h 0468h Trip monitor 7 Limit state
0 to 6
*5
1
046Ah 0469h Trip monitor 7 Special state
0 to 6
*5
1
046Ch 046Ah Trip monitor 7 RUN time
0 to 1000000 1(hr)
046Dh 046Ch
046Eh 046Dh
Trip monitor 7 Power ON
time
0 to 1000000 1(hr)
046Fh 046Eh
0470h 046Fh
Trip monitor 7 Absolute time
(year, month)
00 to 99 (BCD code)
01 to 12 (BCD code)
-
0471h 0470h
Trip monitor 7 Absolute time
(day, day of the week)
01 to 31 (BCD code)
00 to 06 (BCD code)
-
0472h 0471h
Trip monitor 7 Absolute time
(hour, minute)
00 to 23 (BCD code)
00 to 59 (BCD code)
-
0475h 0474h Trip monitor 8 Factor
dE-18 R
1 to 255 1
0476h 0475h
Trip monitor 8 Output fre-
quency
-59000 to 59000 0.01(Hz)
0477h 0476h (with sign)
0478h 0477h
Trip monitor 8 Output cur-
rent
0 to 65535 0.01(A)
0479h 0478h
Trip monitor 8 P-N DC volt-
age
0 to 10000 0.1(Vdc)
047Ah 0479h Trip monitor 8 Inverter state
0 to 8
*5
1
047Bh 047Ah Trip monitor 8 LAD state
0 to 5
*5
1
047Ch 047Bh
Trip monitor 8 INV control
mode
0 to 11
*5
1
047Dh 047Ch Trip monitor 8 Limit state
0 to 6
*5
1
047Eh 047Dh Trip monitor 8 Special state
0 to 6
*5
1
0480h 047Eh Trip monitor 8 RUN time
0 to 1000000 1(hr)
0481h 0480h
0482h 0481h
Trip monitor 8 Power ON
time
0 to 1000000 1(hr)
0483h 0482h
0484h 0483h
Trip monitor 8 Absolute time
(year, month)
00 to 99 (BCD code)
01 to 12 (BCD code)
-
0485h 0484h
Trip monitor 8 Absolute time
(day, day of the week)
01 to 31 (BCD code)
00 to 06 (BCD code)
-
0486h 0485h
Trip monitor 8 Absolute time
(hour, minute)
00 to 23 (BCD code)
00 to 59 (BCD code)
-
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution

Table of Contents

Related product manuals