9 - 33
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-5 Modbus Communication Register Number List
9
9-5-2 Group d Register List
0489h Trip monitor 9 Factor
dE-19 R
1 to 255 1
048Ah 0489h
Trip monitor 9 Output fre-
quency
-59000 to 59000 0.01(Hz)
048Bh 048Ah (with sign)
048Ch 048Bh
Trip monitor 9 Output cur-
rent
0 to 65535 0.01(A)
048Dh 048Ch
Trip monitor 9 P-N DC volt-
age
0 to 10000 0.1(Vdc)
048Eh 048Dh Trip monitor 9 Inverter state
0 to 8
*5
1
048Fh 048Eh Trip monitor 9 LAD state
0 to 5
*5
1
0490h 048Fh
Trip monitor 9 INV control
mode
0 to 11
*5
1
0491h 0490h Trip monitor 9 Limit state
0 to 6
*5
1
0492h 0491h Trip monitor 9 Special state
0 to 6
*5
1
0494h 0493h Trip monitor 9 RUN time
0 to 1000000 1(hr)
0495h 0494h
0496h 0495h
Trip monitor 9 Power ON
time
0 to 1000000 1(hr)
0497h 0496h
0498h 0497h
Trip monitor 9 Absolute time
(year, month)
00 to 99 (BCD code)
01 to 12 (BCD code)
-
0499h 0498h
Trip monitor 9 Absolute time
(day, day of the week)
01 to 31 (BCD code)
00 to 06 (BCD code)
-
049Ah 0499h
Trip monitor 9 Absolute time
(hour, minute)
00 to 23 (BCD code)
00 to 59 (BCD code)
-
049Dh 049Ch Trip monitor 10 Factor
dE-20 R
1 to 255 1
049Eh 049Dh
Trip monitor 10 Output fre-
quency
-59000 to 59000 0.01(Hz)
049Fh 049Eh (with sign)
04A0h 049Fh
Trip monitor 10 Output cur-
rent
0 to 65535 0.01(A)
04A1h 04A0h
Trip monitor 10 P-N DC volt-
age
0 to 10000 0.1(Vdc)
04A2h 04A1h
Trip monitor 10 Inverter
state
0 to 8
*5
1
04A3h 04A2h Trip monitor 10 LAD state
0 to 5
*5
1
04A4h 04A3h
Trip monitor 10 INV control
mode
0 to 11
*5
1
04A5h 04A4h Trip monitor 10 Limit state
0 to 6
*5
1
04A6h 04A5h Trip monitor 10 Special state
0 to 6
*5
1
04A8h 04A7h Trip monitor 10 RUN time
0 to 1000000 1(hr)
04A9h 04A8h
04AAh 04A9h
Trip monitor 10 Power ON
time
0 to 1000000 1(hr)
04ABh 04AAh
04ACh 04ABh
Trip monitor 10 Absolute
time (year, month)
00 to 99 (BCD code)
01 to 12 (BCD code)
-
04ADh 04ACh
Trip monitor 10 Absolute
time (day, day of the week)
01 to 31 (BCD code)
00 to 06 (BCD code)
-
04AEh 04ADh
Trip monitor 10 Absolute
time (hour, minute)
00 to 23 (BCD code)
00 to 59 (BCD code)
-
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution