9 - 65
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-5 Modbus Communication Register Number List
9
9-5-5 Group b Register List
32D4h 32D3h
Torque limit 1 (Forward driv-
ing), 1st-motor
bA112 R/W
0.0 to 500.0 (%)
(Limited at a torque equivalent to
200% of inverter ND rating)
0.1(%)
32D5h 32D4h
Torque limit 2 (Reverse
regenerative), 1st-motor
bA113 R/W
0.0 to 500.0 (%)
(Limited at a torque equivalent to
200% of inverter ND rating)
0.1(%)
32D6h 32D5h
Torque limit 3 (Reverse driv-
ing), 1st-motor
bA114 R/W
0.0 to 500.0 (%)
(Limited at a torque equivalent to
200% of inverter ND rating)
0.1(%)
32D7h 32D6h
Torque limit 4 (Forward regen-
erative), 1st-motor
bA115 R/W
0.0 to 500.0 (%)
(Limited at a torque equivalent to
200% of inverter ND rating)
0.1(%)
32D8h 32D7h
Torque limit LADSTOP
selection, 1st-motor
bA116 R/W
00: Disabled
01: Enabled
-
32DCh 32DBh
Over current suppress
enable, 1st-motor
bA120 R/W
00: Disabled
01: Enabled
-
32DDh 32DCh
Over current suppress Level,
1st-motor
bA121 R/W
(0.0 to 2.0)
× Inverter rated current
*1
0.1(A)
32Deh 32DDh
Overload restriction 1 mode
selection, 1st-motor
bA122 R/W
00: Disabled
01: Accelerate at constant speed
02: Only constant speed
03: Accelerate at constant
speed/Increase speed at regen-
eratio:n
-
32DFh 32Deh
Overload restriction 1 active
level, 1st-motor
bA123 R/W
(0.2 to 2.0)
× Inverter rated current
*1
0.1(A)
32E0h 32DFh
Overload restriction 1 action
time, 1st-motor
bA124
(HIGH)
R/W
10 to 360000 0.01(s)
32E1h 32E0h
bA125
(LOW)
R/W
32E2h 32E1h
Overload restriction 2 mode
selection, 1st-motor
bA126 R/W
00: Disabled
01: Accelerate at constant speed
02: Only constant speed
03: Accelerate at constant
speed/Increase speed at regen-
eratio:n
-
32E3h 32E2h
Overload restriction 2 active
level, 1st-motor
bA127 R/W
(0.2 to 2.0)
× Inverter rated current
*1
0.1(A)
32E4h 32E3h
Overload restriction 2 Action
time, 1st-motor
bA128
(HIGH)
R/W
10 to 360000 0.01(s)
32E5h 32E4h
bA129
(LOW)
R/W
32E6h 32E5h
Deceleration-stop at power
failure
bA-30 R/W
00 (Disabled)/
01 (Enabled: deceleration stop)/
02 (Enabled: no recovery)/
03 (Enabled: with recovery)
-
32E7h 32E6h
Decel-stop at power failure
starting voltage
bA-31 R/W
(200V class) 0- 4100
(400V class) 0- 8200
0.1(Vdc)
32E8h 32E7h
Decel-stop at power failure
control target level
bA-32 R/W
(200V class) 0- 4100
(400V class) 0- 8200
0.1(Vdc)
32Eah 32E9h
Decel-stop at power failure
deceleration time
bA-34
(HIGH)
R/W
1 to 360000 0.01(s)
32Ebh 32EAh
bA-35
(LOW)
R/W
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W Monitor or setting data
Resolution