EasyManua.ls Logo

Omron RX2 Series - Page 661

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 - 69
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-5 Modbus Communication Register Number List
9
9-5-5 Group b Register List
3382h 3381h
Position deviation error detec-
tion level
bb-86 R/W 0 to 65535 (×100pls)
1(×100pl
s)
3383h 3382h
Position deviation error detec-
tion time
bb-87 R/W 0 to 50 0.1(s)
33F5h 33F4h STO input display selection bd-01 R/W
00: With indication
01: Without indication
02: Trip
-
33F6h 33F5h STO input change time bd-02 R/W 0 to 6000 0.01(s)
33F7h 33F6h
Display selection at STO input
change time
bd-03 R/W
00: With indication
01: Without indication
-
33F8h 33F7h
Action selection after STO
input change time
bd-04 R/W
00: Retain only the condition
01: Disabled
02: Trip
-
59D9h 59D8h
Frequency limit selection, 2nd
motor
bA201 R/W Same as bA101 -
59Dah 59D9h
Upper frequency limit, 2nd
motor
bA202 R/W Same as bA102 0.01(Hz)
59DBh 59DAh
Lower frequency limit, 2nd
motor
bA203 R/W Same as bA103 0.01(Hz)
59E2h 59E1h
Torque limit selection,
2nd-motor
bA210 R/W Same as bA110 -
59E3h 59E2h
Torque limit parameter mode
selection, 2nd-motor
bA211 R/W Same as bA111 -
59E4h 59E3h
Torque limit 1 (Forward driv-
ing), 2nd-motor
bA212 R/W Same as bA112 0.1(%)
59E5h 59E4h
Torque limit 2 (Reverse
regenerative), 2nd-motor
bA213 R/W Same as bA113 0.1(%)
59E6h 59E5h
Torque limit 3 (Reverse driv-
ing), 2nd-motor
bA214 R/W Same as bA114 0.1(%)
59E7h 59E6h
Torque limit 4 (Forward regen-
erative), 2nd motor
bA215 R/W Same as bA115 0.1(%)
59E8h 59E7h
Torque limit LADSTOP
selection, 2nd-motor
bA216 R/W Same as bA116 -
59Ech 59EBh
Over current suppress
enable, 2nd-motor
bA220 R/W Same as bA120 1
59Edh 59ECh
Over current suppress Level,
2nd-motor
bA221 R/W Same as bA121 0.1(A)
59Eeh 59EDh
Overload restriction 1 mode
selection, 2nd-motor
bA222 R/W Same as bA122 -
59Efh 59EEh
Overload restriction 1 active
level, 2nd-motor
bA223 R/W Same as bA123 0.1(A)
59F0h 59EFh
Overload restriction 1 action
time, 2nd-motor
bA224
(HIGH)
R/W
Same as bA124 0.01(s)
59F1h 59F0h
bA225
(LOW)
R/W
59F2h 59F1h
Overload restriction 2 mode
selection, 2nd-motor
bA226
R/W
Same as bA126 -
59F3h 59F2h
Overload restriction 2 active
level, 2nd-motor
bA227 R/W Same as bA127 0.1(A)
59F4h 59F3h
Overload restriction 2 action
time, 2nd-motor
bA228
(HIGH)
R/W
Same as bA128 0.01(s)
59F5h 59F4h
bA229
(LOW)
R/W
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W Monitor or setting data
Resolution

Table of Contents

Related product manuals