9 - 69
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-5 Modbus Communication Register Number List
9
9-5-5 Group b Register List
3382h 3381h
Position deviation error detec-
tion level
bb-86 R/W 0 to 65535 (×100pls)
1(×100pl
s)
3383h 3382h
Position deviation error detec-
tion time
bb-87 R/W 0 to 50 0.1(s)
33F5h 33F4h STO input display selection bd-01 R/W
00: With indication
01: Without indication
02: Trip
-
33F6h 33F5h STO input change time bd-02 R/W 0 to 6000 0.01(s)
33F7h 33F6h
Display selection at STO input
change time
bd-03 R/W
00: With indication
01: Without indication
-
33F8h 33F7h
Action selection after STO
input change time
bd-04 R/W
00: Retain only the condition
01: Disabled
02: Trip
-
59D9h 59D8h
Frequency limit selection, 2nd
motor
bA201 R/W Same as bA101 -
59Dah 59D9h
Upper frequency limit, 2nd
motor
bA202 R/W Same as bA102 0.01(Hz)
59DBh 59DAh
Lower frequency limit, 2nd
motor
bA203 R/W Same as bA103 0.01(Hz)
59E2h 59E1h
Torque limit selection,
2nd-motor
bA210 R/W Same as bA110 -
59E3h 59E2h
Torque limit parameter mode
selection, 2nd-motor
bA211 R/W Same as bA111 -
59E4h 59E3h
Torque limit 1 (Forward driv-
ing), 2nd-motor
bA212 R/W Same as bA112 0.1(%)
59E5h 59E4h
Torque limit 2 (Reverse
regenerative), 2nd-motor
bA213 R/W Same as bA113 0.1(%)
59E6h 59E5h
Torque limit 3 (Reverse driv-
ing), 2nd-motor
bA214 R/W Same as bA114 0.1(%)
59E7h 59E6h
Torque limit 4 (Forward regen-
erative), 2nd motor
bA215 R/W Same as bA115 0.1(%)
59E8h 59E7h
Torque limit LADSTOP
selection, 2nd-motor
bA216 R/W Same as bA116 -
59Ech 59EBh
Over current suppress
enable, 2nd-motor
bA220 R/W Same as bA120 1
59Edh 59ECh
Over current suppress Level,
2nd-motor
bA221 R/W Same as bA121 0.1(A)
59Eeh 59EDh
Overload restriction 1 mode
selection, 2nd-motor
bA222 R/W Same as bA122 -
59Efh 59EEh
Overload restriction 1 active
level, 2nd-motor
bA223 R/W Same as bA123 0.1(A)
59F0h 59EFh
Overload restriction 1 action
time, 2nd-motor
bA224
(HIGH)
R/W
Same as bA124 0.01(s)
59F1h 59F0h
bA225
(LOW)
R/W
59F2h 59F1h
Overload restriction 2 mode
selection, 2nd-motor
bA226
R/W
Same as bA126 -
59F3h 59F2h
Overload restriction 2 active
level, 2nd-motor
bA227 R/W Same as bA127 0.1(A)
59F4h 59F3h
Overload restriction 2 action
time, 2nd-motor
bA228
(HIGH)
R/W
Same as bA128 0.01(s)
59F5h 59F4h
bA229
(LOW)
R/W
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W Monitor or setting data
Resolution