Compliance Criteria
l Guarantees that the conditions for an FSP 3000 C are potentially met up to Hazard
Level 1M (IEC 60825-2 and ANSI Z136);
l Is clean and dry, allowing enough space for future network connections and expansion
as needed;
l Is protected from water both from above and on the floor; and
l Is protected from excessive heat, direct sunlight, dust, or chemical exposure.
Exposure might cause temperatures to exceed the specified limits and result in
incorrect operation or damage to the equipment.
l Environmental Specifications
l Local Building and National Electrical Codes Warning
l Restricted Access Area Warning
Compliance Criteria
While planning your site, it is important to note that the FSP 3000 C system adheres to
the following site compliance criteria:
Environment
l NEBS Level 3 and ETSI EN 300 019-1-3
(2004)
Degree of Protection
l IP20 degree of protection according to IEC
60529
l Use in a Pollution Degree 2 environment
Acoustic Noise Emissions
l Produces sound levels less than 60 dBA
l Meets the requirements of the GR-63-
CORE, Issue April 2012, Ch. 4.6 and ETSI
ETS 300 753 (Jan 2012) standards
Electromagnetic Interference and
Electrical Safety
l Telcordia standard GR-1089-CORE, Issue
3, May 2011 regarding EMC and electrical
safety
l EMC Directive 2014/30/EU
l Low Voltage Directive (LVD) 2014/35/EU
l Suitable for installation as part of the
Common Bonding Network (BN)
l Installation Safety Guidelines and Warnings
l Agency Approvals and Regulatory Compliance Information