Power Cables
For North America, the power cable:
l Must be no longer than 4.5 meters (14.76 ft). Contact a qualified
electrician for additional assistance.
l Must be UL Listed/CSA Certified, SVT type and rated 105°C (221°F).
The cable should have three conductors of minimum No. 18 AWG
and is fitted with an female end IEC-320-C13 appliance coupler and a
NEMA 5-15P or NEMA 6-20P attachment connector.
l Power
l PSM-AC4
l AC Power Electrical Safety Guidelines and Warnings
l Providing Power to the Shelves
1
Except Switzerland and Denmark
Number of ACPower Cables
For redundancy, one AC power cable is required per PSM-AC4. The type of the power
cable depends on the region or country where the FSP 3000 C is installed and the line
power voltage available at the installation site. One power cable is used for primary power
supply (Power A) and the other for backup power supply (Power B).
l Power
l PSM-AC4
l AC Power Electrical Safety Guidelines and Warnings
l Providing Power to the Shelves
CBL/AC/250/LA-C19
The CBL/AC/250/LA-C19 is a flexible, detachable AC power cable. The cable has three
conductors of minimum 1.5 mm
2
cross sectional area or 18 AWG and are assembled
with an IEC-320-C13 appliance coupler on its female end. The AC wall attachment
connector on the male end of the cable must be a country-specific, three-conductor
grounding type that fits only the corresponding grounding-type power outlet.
Cable Type ACPower Cable
Compatible Components
l SH4R
o
PSM-AC4
Length 2.5 meters (8.203 ft)
FSP3000 C Hardware Guide - R1.1 - Issue:A (12/09/2016) 159