SH12 Shelf
Parameter Value Notes
Power consumption
(fully equipped with 20 traffic
modules)
2900 W @ –48 VDC Typical
3913 W @ –48 VDC Maximum
Maximum power 1+0 (non-redundant) and
1+1 (redundant)
configurations
l 1304 W @ –48 V
l 27 A @ –48 V
2+0 (non-redundant) and
2+1 (redundant)
configurations
l 2608 W @ –48 V
l 54 A @ –48 V
3+0 (non-redundant) and
3+1 (redundant)
configurations
l 3913 W @ –48 V
l 82 A @ –48 V
Maximum internal power
l 1+0 and 1+1: 1200 W
l 2+0 and 2+1: 2400 W
l 3+0 and 3+1: 3600 W
Environmental standards
compliance
l Telcordia SR-3580 Level 3 (NEBS)
l ETSI EN 300 019-1-3 Class 3.1
l IEC 60529 IP20 (indoor office)
Table 2: General Information — SH12
l Environmental Specifications
l Power
l MTBF Hours for FSP 3000 C Equipment
l Infrastructure Modules
l Traffic Module Compatibility
l Accessories
l Installation Overview — SH12 and SH4R Shelves
l Permissible Configurations
Features
l Provides high-density support for all traffic modules
l Has a front access architecture
l Supports 2-zone ground configuration
24 FSP3000 C Hardware Guide - R1.1 - Issue:A (12/09/2016)