Mounting the SH4R Shelf to a Rack
EQUIPMENT DAMAGE MAY RESULT IF:
You lift the shelf by inserting your hands into the shelf. Lift from the
outside of the shelf to avoid damage.
While positioning the shelf into the rack, keep hold of the grounding cable,
which is attached on the shelf’s right side or reverse side, to not
inadvertently jam it.
Figure 58: SH4R Sitting on Guide Rails in a 19-inch Rack Rear View
10. Attach the other end of the grounding cable to the cage nut affixed in Step 8 or to the
preinstalled terminal connector used for the ground point on the rack to ensure
adequate grounding for the shelf.
11. Use a Pozidriv screwdriver and the appropriate screw/washer or a screw (for the
preinstalled terminal connector) to secure the grounding cable to the rack.
12. Use a multimeter to test the grounding connection. The continuity between the shelf
and the rack’s ground point should measure zero Ohms of resistance.
ELECTRIC VOLTAGEWARNING
Testing the grounding connection must be performed only by
service personnel or a qualified/licensed electrician.
13. Repeat this procedure for installing additional shelves in the rack.
208 FSP3000 C Hardware Guide - R1.1 - Issue:A (12/09/2016)