Proline Promag 300 Modbus RS485 Modbus RS485 Register Information
Endress+Hauser 235
"Config. backup" submenu
Navigation: Expert → System → Config. backup
Parameter Register Data type Access Selection / User entry / User interface →
Operating time (0652) 2631 Integer Read Days (d), hours (h), minutes (m) and
seconds (s)
28
Last backup (2757) 6430 Integer Read Days (d), hours (h), minutes (m) and
seconds (s)
29
Config. managem. (2758) 5500 Integer Read / Write 0 = Cancel
1 = Execute backup
2 = Restore
4 = Clear backup
5 = Compare
29
Backup state (2759) 5502 Integer Read 1 = Backup in progr.
2 = Restore in progr
4 = Delete in progr.
5 = Comp. in progr.
6 = Restoring failed
7 = Backup failed
251 = None
30
Compar. result (2760) 5514 Integer Read 0 = Set. identical
1 = Set. not ident.
2 = No backup
3 = Check not done
4 = Backup corrupt
5 = Dataset incomp.
30
"Diagn. handling" submenu
Navigation: Expert → System → Diagn. handling
Parameter Register Data type Access Selection / User entry / User interface →
Alarm delay (0651) 6808 to 6809 Float Read / Write 0 to 60 s 31
"Diagn. behavior" submenu
Navigation: Expert → System → Diagn. handling → Diagn. behavior
Parameter Register Data type Access Selection / User entry / User interface →
Diagnostic no. 302 (0739) 2312 Integer Read / Write 2 = Warning
3 = Alarm
33
Diagnostic no. 531 (0741) 2397 Integer Read / Write 0 = Off
1 = Logbook only
2 = Warning
3 = Alarm
36
Diagnostic no. 441 (0657) 4742 Integer Read / Write 0 = Off
1 = Logbook only
2 = Warning
3 = Alarm
34
Diagnostic no. 442 (0658) 4919 Integer Read / Write 0 = Off
1 = Logbook only
2 = Warning
3 = Alarm
35
Diagnostic no. 443 (0659) 5000 Integer Read / Write 0 = Off
1 = Logbook only
2 = Warning
3 = Alarm
35