Troubleshooting the MX480 PICs
Problem Description: The PICs are not functioning normally.
Solution Check the status of each port on a PIC by looking at the LED located on the PIC
faceplate. For information about the meaning of LED states on different PICs, see the
MX Series Interface Module Reference.
Check the status of a PIC by issuing the show chassis fpc pic-status CLI command. The
PIC slots in the FPC are numbered from 0 through 1, left to right:
user@host> show chassis fpc pic-status
Slot 0 Online DPC 40x 1GE R
PIC 0 Online 10x 1GE(LAN)
PIC 1 Online 10x 1GE(LAN)
PIC 2 Online 10x 1GE(LAN)
PIC 3 Online 10x 1GE(LAN)
Slot 1 Online MX FPC Type 3
PIC 0 Online 1x OC-192 SONET
PIC 1 Online 1x OC-192 SONET
Slot 2 Online MS-DPC
PIC 0 Online MS-DPC PIC
PIC 1 Online MS-DPC PIC
Slot 3 Online MPC Type 2 3D EQ
PIC 0 Online 1x 10GE XFP
PIC 1 Online 1x 10GE XFP
Slot 4 Online MPC 3D 16x 10GE
PIC 0 Online 4x 10GE(LAN) SFP+
PIC 1 Online 4x 10GE(LAN) SFP+
PIC 2 Online 4x 10GE(LAN) SFP+
PIC 3 Online 4x 10GE(LAN) SFP+
For further description of the output from the command, see the CLI Explorer.
Related
Documentation
MX480 Flexible PIC Concentrator (FPC) Description on page 63
Replacing an MX480 PIC on page 350
Maintaining MX480 PICs on page 433
MX480 PIC Serial Number Label on page 468
Troubleshooting the MX480 Power System
Problem Description: The power system is not functioning normally.
Solution Check the LEDs on each power supply faceplate.
If an AC power supply is correctly installed and functioning normally, the AC OK and
DC OK LED’s light steadily, and the PS FAIL LED is not lit.