11.9 H: TERMINALS
350 SIEPCYEUOQ2V01A Q2V Technical Manual
Setting Value Function Description Ref.
11 LOC/REM Sel.
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
ON : LOCAL
OFF : REMOTE
573
12 AI Input Sel
Sets the command that enables or disables the terminals selected in H3-14 [An.In Term.Enable Sel].
ON : Input to the terminal selected with H3-14 is enabled
OFF : Input to the terminal selected with H3-14 is disabled
574
15 FWD/REV Det
Set the motor rotation direction when you use Simple Closed Loop V/f Control method.
ON : Reverse run
OFF : Forward run
574
16 Ref Sample
Sets the command to sample the frequency reference at terminal AI1 or AI2, and hold the frequency reference at
that frequency.
574
17 Ac/Dec Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output
frequency that was stored in the drive at the time of the pause, and restarts motor operation.
574
18 Ac/Dec Time1
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/Deceleration Time 2 [C1-
03, C1-04].
575
19 Ac/Dec Time2
Set this function and H1-xx = 18 [Ac/Dec Time1] together. Sets the drive to use Acceleration/Deceleration Time 3
[C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07, C1-08].
575
1A Drive Enable
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands when the terminal is
OFF.
575
1B Baseblock NO
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
ON : Baseblock (drive output stop)
OFF : Normal operation
575
1E Baseblock NC
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
ON : Normal operation
OFF : Baseblock (drive output stop)
576
20 to 2F External Fault
Sets a command to stop the drive when a failure or fault occurs on an external device.
20 : External Fault (ExF NO-AlRmp)
21 : External Fault (ExF NC-AlRmp)
22 : External Fault (ExF NO-RnRmp)
23 : External Fault (ExF NC-RnRmp)
24 : External Fault (ExF NO-AlCoast)
25 : External Fault ExF NC-AlCoast)
26 : External Fault (ExF NO-RnCoast)
27 : External Fault (ExF NC-RnCoast)
28 : External Fault (ExF NO-AlFStop)
29 : External Fault (ExF NC-AlFStop)
2A : External Fault (ExF NO-RnFStop)
2B : External Fault (ExF NC-RnFStop)
2C : External Fault (ExF NO-AlAlarm)
2D : External Fault (ExF NC-AlAlarm)
2E : External Fault (ExF NO-RnAlarm)
2F : External Fault (ExF NC-RnAlarm)
576
30 DCInj Cmd
Sets the command to use DC Injection Braking to stop the motor.
Note:
When A1-02 = 8 [Control Method = EZ Vector], this function is available only when you use a PM motor.
577
32 HiSlipBraking
Sets the command to use high-slip braking to stop the motor.
577
34 Fast Stop NO
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
577
35 Fast Stop NC
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
577