12.7 H: TERMINALS
SIEPCYEUOQ2V01A Q2V Technical Manual 589
■ H2-01: NO,NC,CM FuncSelection
No.
(Hex.)
Name Description
Default
(Range)
H2-01
(040B)
NO,NC,CM FuncSelection
Sets the function set for MFDO terminal NO-CM or NC-CM.
3
(0 - 1FF)
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in through mode.
■ H2-02: DO1-O1C Func Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-02
(040C)
DO1-O1C Func Selection
Sets the function for MFDO terminal DO1-O1C.
5
(0 - 1FF)
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in through mode.
■ H2-03: DO2-O2C Func Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-03
(040D)
DO2-O2C Func Selection
Sets the function for MFDO terminal DO2-O2C.
F
(0 - 1FF)
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in through mode.
■ H2-06: kWH Out Unit Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-06
(0437)
kWH Out Unit Selection
Sets the unit for the output signal when H2-01 to H2-03 = 65 [MFDO Function Select = WattH
Pulse].
1
(1 - 5)
This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. This parameter sets the kWh
unit for each pulse output.
Figure 12.75 Example MFDO when Configured for Watt Hours
Note:
• When the power value is a negative value (regenerative state), the drive does not count Watt hours.
• When the control power supply to the drive is operating, the drive will keep the Watt hours. If a momentary power loss causes the drive
to lose control power, the Watt hour count will reset.
1 : 0.1 kWh units
2 : 1 kWh units
3 : 10 kWh units
4 : 100 kWh units
5 : 1000 kWh units