12.7 H: TERMINALS
590 SIEPCYEUOQ2V01A Q2V Technical Manual
■ H2-07: Mbus Reg1 Address Select
No.
(Hex.)
Name Description
Default
(Range)
H2-07
(0B3A)
Mbus Reg1 Address Select
Sets the address of the Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets the address of the register that is output to ModbusReg 1 [H2-01 to H2-03 = 67] and uses the bit in H2-08
[Mbus Reg1 Bit Select].
■ H2-08: Mbus Reg1 Bit Select
No.
(Hex.)
Name Description
Default
(Range)
H2-08
(0B3B)
Mbus Reg1 Bit Select
Sets the bit of the Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to ModbusReg 1 [H2-01 to H2-03 = 67] and uses the address in H2-07
[Mbus Reg1 Address Select].
■ H2-09: Mbus Reg2 Address Select
No.
(Hex.)
Name Description
Default
(Range)
H2-09
(0B3C)
Mbus Reg2 Address Select
Sets the address of the Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets the address of the register that is output to ModbusReg 1 [H2-01 to H2-03 = 67] and uses the bit in H2-10
[Mbus Reg2 Bit Select].
■ H2-10: Mbus Reg2 Bit Select
No.
(Hex.)
Name Description
Default
(Range)
H2-10
(0B3D)
Mbus Reg2 Bit Select
Sets the bit of the Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to ModbusReg 1 [H2-01 to H2-03 = 67] and uses the address in H2-09
[Mbus Reg2 Address Select].
■ H2-20: Compare1 Mon.Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-20
(1540)
Compare1 Mon.Selection
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example,
set H2-20 = 102 to monitor U1-02 [Output Frequency].
102
(000 - 999)
Note:
• For information on the comparator function, refer to 3C: Comparator 1 on page 605 and 3D: Comparator 2 on page 605.
• The configurable monitor changes when the control method changes.
■ H2-21: Compare1 Low Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-21
(1541)
Compare1 Low Limit
Sets the lower limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to 3C: Comparator 1 on page 605 and 3D: Comparator 2 on page 605.
■ H2-22: Compare1 Up Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-22
(1542)
Compare1 Up Limit
Sets the upper limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
0.0%
(0.0 - 300.0%)