8 Applied Settings
8 - 10
High-function General-purpose Inverter RX2 Series User’s Manual
Input Terminal Function
Data Monitor Function
Item Terminal name Data Description
PID disable function [PID] 041
Disables the PID1 function by turning ON the terminal
function. When disabled, operation is done by using
the command set for target value as command fre-
quency.
PID1 I control inte-
gral value clear
[PIDC] 042 Clears integral value of PID1 control.
Multi-layer target
command terminal 1
[SVC1] 051
Switches multiple target values.
Multi-layer target
command terminal 2
[SVC2] 052
Multi-layer target
command terminal 3
[SVC3] 053
Multi-layer target
command terminal 4
[SVC4] 054
PID gain switch [PRO] 055 Switches PID gain 1 and 2 by terminal.
Item Parameter Data Description
PID1 target value 1 [FA-30]
0.00 to 100.00(%)
*1
*1. Data range varies depending on the data from [AH-04] to [AH-06].
Displays PID1 target value.
Is changeable when [AH-07] = 07 or
multi-layer target value 1-15 is enabled.
PID1 target value 2 [FA-32]
0.00 to 100.00(%)
*1
Displays PID1 target value 2.
Is changeable when [AH-42] = 07.
PID1 target value 3 [FA-34]
0.00 to 100.00(%)
*1
Displays PID1 target value 3.
Is changeable when [AH-46] = 07.
PID1 feedback data 1
monitor
[db-30]
-100.00 to 100.00(%)
*1
Displays PID1 feedback value 1.
PID1 feedback data 2
monitor
[db-32]
-100.00 to 100.00(%)
*1
Displays PID1 feedback value 2.
PID1 feedback data 3
monitor
[db-34]
-100.00 to 100.00(%)
*1
Displays PID1 feedback value 3.
PID1 target value monitor
after calculation
[db-42]
-100.00 to 100.00(%)
*1
Displays target value after calculation by
[AH-50].
PID1 feedback data [db-44]
-100.00 to 100.00(%)
*1
Displays feedback value after calculation
by [AH-54].
PID1 output monitor [db-50] -100.00 to 100.00(%) Displays PID1 output value.
PID1 deviation monitor [db-51] -200.00 to 200.00(%) Displays PID1 deviation.
PID1 deviation 1 monitor [db-52] -200.00 to 200.00(%)
Monitors 3 deviations of PID1 when
[AH-50] = 05 or 06.
PID1 deviation 2 monitor [db-53] -200.00 to 200.00(%)
PID1 deviation 3 monitor [db-54] -200.00 to 200.00(%)
PID current P gain monitor [db-61] 0.0 to 100.0 Displays current P gain.
PID current I gain monitor [db-62] 0.0 to 3600.0(s) Displays current I gain.
PID current D gain monitor [db-63] 0.00 to 100.00(s) Displays current D gain.
PID feed-forward monitor [db-64] -100.00 to 100.00(%) Displays feed-forward command value.