8 - 189
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-11 Output Terminal Function
8
8-11-6 Output Functions (FM)
With the “Bias adjustment [Cd-13]” of the “Digital frequency output,” you can bias Point 0 as shown in
the below figure.
(Ex.) Digital-frequency-outputting information on [dA-01] output frequency monitor
Output so that the maximum values of the digital frequency output corresponds to the maximum fre-
quency.
When the maximum frequency is 60 Hz, set [Cd-02]=60Hz.
[Cd-13]=0.0%, [Cd-14]=100.0%
With the “Gain adjustment [Cd-14]” of the “Digital frequency output,” you can change an inclination as
shown in the below figure.
[Cd-01] [FM] Terminal Output Form Selection is Set to 01
[Cd-02]
0
[Cd-13]=50.0(%)
[Cd-13]= -50.0(%)
[Cd-13]=0.0(%)
0
[Cd-02]/2
-[Cd-02]/2
Output scale
Outputting will
be made in this
range.
Maximum
Parallel
movement
Digital frequency (Hz)
60Hz
0
60Hz
0Hz
30Hz
30Hz
Maximum frequency
Output frequency (Hz)
Digital frequency (Hz)
0
[Cd-14]=200.0(%)
[Cd-14]=50.0(%)
[Cd-14]=100.0(%)
0
[Cd-14]=-50.0(%)
[Cd-02]
[Cd-02]/2
-[Cd-02]/2
Full scale (FS)
Outputting will
be made in this
range.
Maximum
Change in
inclination
Digital
frequency (Hz)