8 Applied Settings
8 - 190
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.) Digital-frequency-outputting information on [dA-02] output current monitor
When a current equivalent to inverter rated current flows, provide output at 1,500 Hz.
Set [Cd-02]=3000Hz.
[Cd-13]=0.0%, [Cd-14]=100.0%
Set [Cd-02]=1500Hz.
[Cd-13]=0.0%, [Cd-14]=200.0%
Setting the analog monitor adjustment mode [Cd-10] to 01 fixes the output of the [FM] output terminal.
With the fixed output, an output set with [Cd-12] is made for the full-scale value of the monitor selected
with [Cd-03].
(Ex.) Outputting the output current monitor with the PWM output
When a current equivalent to inverter rated current flows, provide output with a PWM output at 100%.
(The standard point is the inverter rated current.)
1 Set [Cd-01]=00 and [Cd-03]=(dA-02).
Setting [Cd-10] to 01 outputs PWM from the [FM] terminal in accordance with [Cd-12].
Analog Monitor Adjustment Mode: [FM] Output
Code Name
Output scale range
(Corresponding to 0 to 10 V /
0 to 20 mA)
dA-02 Output current monitor
(0.00 to 2.00) ×
Inverter rated current (A)
Rated current × 2 (A)
Output current (A)
Rated current
(A)
Digital frequency (Hz)
Rated current × 2 (A)
Output current (A)
Rated current
(A)
Digital frequency (Hz)