9 - 67
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-5 Modbus Communication Register Number List
9
9-5-5 Group b Register List
332Dh 332Ch
Carrier speed setting,
1st-motor
bb101 R/W
[Ub-03]=02: ND
0.5 to 16.0 (kHz)
[Ub-03]=01: LD
0.5 to 12.0 (kHz)
[Ub-03]=00: VLD
0.5 to 10.0 (kHz)
*3
0.1kHz
332Eh 332Dh
Sprinkle carrier pattern
selection, 1st-motor
bb102 R/W
00: Disabled
01: Pattern 1 enabled
02: Pattern 2 enabled
03: Pattern 3 enabled
-
332Fh 332Eh
Automatic-carrier reduction
selection, 1st-motor
bb103 R/W
00: Disabled
01: Enabled: current
02: Enabled: temperature
-
3336h 3335h
Automatic error reset
selection
bb-10 R/W
00: Disabled
01: Enabled with operation com-
mand OFF
02: Enable after the setting time
-
3337h 3336h
Alarm signal selection at
Automatic error reset is active
bb-11 R/W
00: Output
01: Not output
-
3338h 3337h
Automatic error reset wait
time
bb-12 R/W 0 to 600 1(s)
3339h 3338h Automatic error reset number bb-13 R/W 0 to 10 1
3340h 3339h
The number of retries after
instantaneous power failure
bb-20 R/W 0 to 16 / 255 1
3341h 3340h
The number of retries after
under voltage
bb-21 R/W 0 to 16 / 255 1
3342h 3341h
The number of retries after
over current
bb-22 R/W 0 to 5 1
3343h 3342h
The number of retries after
over voltage
bb-23 R/W 0 to 5 1
3344h 3343h
Selection of restart mode
@Instantaneous power fail-
ure/ under-voltage trip
bb-24 R/W
00: 0Hz
01: (Frequency matching
02: Frequency entrainment
03: Detection speed
04: Trip after frequency matching
deceleration stop
-
3345h 3344h
Allowable under-voltage
power failure time
bb-25 R/W 3 to 250 0.1(s)
3346h 3345h
Retry wait time before motor
restart
bb-26 R/W 3 to 1000 0.1(s)
3347h 3346h
Instantaneous power fail-
ure/under-voltage trip alarm
enable
bb-27 R/W
00: Disabled
01: Enabled at stop
02: Disabled at stop and deceler-
ation stop
-
3348h 3347h
Selection of restart mode
@over-current
bb-28 R/W
00: 0Hz
01: Frequency matching
02: Frequency entrainment
03: Detection speed
04: Trip after frequency matching
deceleration stop
-
3349h 3348h
Wait time of restart
@over-current
bb-29 R/W 3 to 1000 0.1(s)
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W Monitor or setting data
Resolution