9 - 75
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-5 Modbus Communication Register Number List
9
9-5-6 Group C Register List
373Ch 373Bh Thermistor selection Cb-40 R/W
00: Disabled
01: PTC resistance value
enabled
02: NTC resistance value
enabled
-
373Dh 373Ch Thermistor gain adjustment Cb-41 R/W 0 to 10000 0.1
3779h 3778h Output terminal [11] function CC-01 R/W
See <List of output terminal func-
tions> on page C-49.
-
377Ah 3779h Output terminal [12] function CC-02 R/W
377Bh 377Ah Output terminal [13] function CC-03 R/W
377Ch 377Bh Output terminal [14] function CC-04 R/W
377Dh 377Ch Output terminal [15] function CC-05 R/W
377Eh 377Dh
Relay output terminal [16]
function
CC-06 R/W
377Fh 377Eh
Relay output terminal [AL]
function
CC-07 R/W
3783h 3782h
Output terminal [11] active
state
CC-11 R/W
00: Normally open: NO
01: Normally closed: NC
-
3784h 3783h
Output terminal [12] active
state
CC-12 R/W
3785h 3784h
Output terminal [13] active
state
CC-13 R/W
3786h 3785h
Output terminal [14] active
state
CC-14 R/W
3787h 3786h
Output terminal [15] active
state
CC-15 R/W
3788h 3787h
Output terminal [16] active
state
CC-16 R/W
3789h 3788h
Output terminal [AL] active
state
CC-17 R/W
378Ch 378Bh
Output terminal [11] on-delay
time
CC-20 R/W 0 to 10000 0.01(s)
378Dh 378Ch
Output terminal [11] off-delay
time
CC-21 R/W 0 to 10000 0.01(s)
378Eh 378Dh
Output terminal [12] on-delay
time
CC-22 R/W 0 to 10000 0.01(s)
378Fh 378Eh
Output terminal [12] off-delay
time
CC-23 R/W 0 to 10000 0.01(s)
3790h 378Fh
Output terminal [13] on-delay
time
CC-24 R/W 0 to 10000 0.01(s)
3791h 3790h
Output terminal [13] off-delay
time
CC-25 R/W 0 to 10000 0.01(s)
3792h 3791h
Output terminal [14] on-delay
time
CC-26 R/W 0 to 10000 0.01(s)
3793h 3792h
Output terminal [14] off-delay
time
CC-27 R/W 0 to 10000 0.01(s)
3794h 3793h
Output terminal [15] on-delay
time
CC-28 R/W 0 to 10000 0.01(s)
3795h 3794h
Output terminal [15] off-delay
time
CC-29 R/W 0 to 10000 0.01(s)
3796h 3795h
Output relay [16] on-delay
time
CC-30 R/W 0 to 10000 0.01(s)
3797h 3796h
Output relay [16] off-delay
time
CC-31 R/W 0 to 10000 0.01(s)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution