9 - 77
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-5 Modbus Communication Register Number List
9
9-5-6 Group C Register List
37B0h 37AFh
Logical calculation target 2
selection of LOG6
CC-56 R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37B1h 37B0h
Logical calculation symbol
selection of LOG6
CC-57 R/W
00:AND
01:OR
02:XOR
-
37B2h 37B1h
Logical calculation target 1
selection of LOG7
CC-58 R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37B3h 37B2h
Logical calculation target 2
selection of LOG7
CC-59 R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37B4h 37B3h
Logical calculation symbol
selection of LOG7
CC-60 R/W
00:AND
01:OR
02:XOR
-
37DDh 37DCh
[FM] monitor output wave
form selection
Cd-01 R/W
00: PWM
01: frequency
-
37Deh 37DDh
[FM] monitor output base fre-
quency (at PWM output)
Cd-02 R/W 0 to 3600 1(Hz)
37DFh 37DEh [FM] monitor output selection Cd-03 R/W
See the List of output monitor
functions
*1
1
37E0h 37DFh [Ao1] monitor output selection Cd-04 R/W
See the List of output monitor
functions
*1
1
37E1h 37E0h [Ao2] monitor output selection Cd-05 R/W
See the List of output monitor
functions
*1
1
37E6h 37E5h
Analog monitor adjust mode
enable
Cd-10 R/W
00: Disabled
01: Enabled
-
37E7h 37E6h
Filter time constant of
[FM]monitor
Cd-11 R/W 1 to 500 1(ms)
37E8h 37E7h [FM] Data type selection Cd-12 R/W
00: absolute value
01: with sign
-
37E9h 37E8h [FM] monitor bias adjustment Cd-13 R/W -1000 to 1000 0.1(%)
37Eah 37E9h [FM] monitor gain adjustment Cd-14 R/W -10000 to 10000 0.1(%)
37Ebh 37EAh
Output level setting at [FM]
monitor adjust mode
Cd-15 R/W -1000 to 1000 0.1(%)
37F1h 37F0h
Filter time constant of [Ao1]
monitor
Cd-21 R/W 1 to 500 1(ms)
37F2h 37F1h [Ao1] Data type selection Cd-22 R/W
00: absolute value
01: with sign
-
37F3h 37F2h [Ao1] monitor bias adjustment Cd-23 R/W -1000 to 1000 0.1(%)
37F4h 37F3h [Ao1] monitor gain adjustment Cd-24 R/W -10000 to 10000 0.1(%)
37F5h 37F4h
Output level setting at [Ao1]
monitor adjust mode
Cd-25 R/W -1000 to 1000 0.1(%)
37FBh 37FAh
Filter time constant of [Ao2]
monitor
Cd-31 R/W 1 to 500 1(ms)
37FCh 37FBh [Ao2] Data type selection Cd-32 R/W
00: absolute value
01: with sign
-
37FDh 37FCh [Ao2] monitor bias adjustment Cd-33 R/W -1000 to 1000 0.1(%)
37Feh 37FDh [Ao2] monitor gain adjustment Cd-34 R/W -10000 to 10000 0.1(%)
37FFh 37FEh
Output level setting at [Ao2]
monitor adjust mode
Cd-35 R/W -1000 to 1000 0.1(%)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data