EasyManua.ls Logo

Omron RX2 Series - Page 882

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendices C Table of Parameters
C - 34
High-function General-purpose Inverter RX2 Series User’s Manual
Parameter Mode (Code B)
Code
Codes that
can be
changed
during
operation
Name Data range Initial value Note
bA101 -
Frequency limit selection,
1st-motor
00 (Disabling)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/03 (Ai3 terminal input)/
04 (Reserved)/05 (Reserved)/06 (Reserved)/
07 (Parameter setting)/08 (RS485)/09 (Option 1)/
10 (Option 2)/11 (Option 3)/
12 (Pulse string input (main body))/
13 (Pulse string input Option)
00
bA102
Upper Frequency limit,
1st-motor
0.00 to 590.00 (Hz) 0.00
bA103
Lower Frequency limit,
1st-motor
0.00 to 590.00 (Hz) 0.00
bA110 - Torque limit selection, 1st-motor
00 (Disable)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/03 (Ai3 terminal input)/
04 (Reserved)/05 (Reserved)/06 (Reserved)/
07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)
07
bA111 -
Torque limit parameter mode
selection, 1st-motor
00 (Four quadrant specific)/
01 ([TRQ] terminal switch)
00
bA112
Torque limit 1 (Forward driving),
1st-motor
0.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of
inverter ND rating)
150.0
bA113
Torque limit 2 (Reverse regener-
ative), 1st-motor
0.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of
inverter ND rating)
150.0
bA114
Torque limit 3 (Reverse driv-
ing), 1st-motor
0.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of
inverter ND rating)
150.0
bA115
Torque limit 4 (Forward regener-
ative), 1st-motor
0.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of
inverter ND rating)
150.0
bA116 -
Torque limit LADSTOP selec-
tion, 1st-motor
00 (Disabled)/01 (Enabled) 00
bA120 -
Over current suppress enable,
1st-motor
00 (Disabled)/01 (Enabled) 01
bA121 -
Over current suppress Level,
1st-motor
(0.0 to 2.0)
× Inverter rated current (A)
*1
*2
bA122 -
Overload restriction 1 mode
selection, 1st-motor
00 (Disabled)/
01 (Accelerate at constant speed)/
02 (Only constant speed)/
03 (Accelerate at constant speed/Increase speed
at regeneration)
01
bA123
Overload restriction 1 active
level, 1st-motor
(0.2 to 2.0)
× Inverter rated current (A)
*1
*3
bA124
Overload restriction 1 action
time, 1st-motor
0.10 to 3600.00 (s) 1.00
bA126 -
Overload restriction 2 mode
selection, 1st-motor
00 (Disabled)/
01 (Accelerate at constant speed)/
02 (Only constant speed)/
03 (Accelerate at constant speed/Increase speed
at regeneration)
01
bA127
Overload restriction 2 active
level, 1st-motor
(0.2 to 2.0)
× Inverter rated current (A)
*1
*3
bA128
Overload restriction 2 Action
time, 1st-motor
0.10 to 3600.00 (s) 1.00

Table of Contents

Related product manuals