Appendices C Table of Parameters
C - 34
High-function General-purpose Inverter RX2 Series User’s Manual
Parameter Mode (Code B)
Code
Codes that
can be
changed
during
operation
Name Data range Initial value Note
bA101 -
Frequency limit selection,
1st-motor
00 (Disabling)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/03 (Ai3 terminal input)/
04 (Reserved)/05 (Reserved)/06 (Reserved)/
07 (Parameter setting)/08 (RS485)/09 (Option 1)/
10 (Option 2)/11 (Option 3)/
12 (Pulse string input (main body))/
13 (Pulse string input Option)
00
bA102
Upper Frequency limit,
1st-motor
0.00 to 590.00 (Hz) 0.00
bA103
Lower Frequency limit,
1st-motor
0.00 to 590.00 (Hz) 0.00
bA110 - Torque limit selection, 1st-motor
00 (Disable)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/03 (Ai3 terminal input)/
04 (Reserved)/05 (Reserved)/06 (Reserved)/
07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)
07
bA111 -
Torque limit parameter mode
selection, 1st-motor
00 (Four quadrant specific)/
01 ([TRQ] terminal switch)
00
bA112
Torque limit 1 (Forward driving),
1st-motor
0.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of
inverter ND rating)
150.0
bA113
Torque limit 2 (Reverse regener-
ative), 1st-motor
0.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of
inverter ND rating)
150.0
bA114
Torque limit 3 (Reverse driv-
ing), 1st-motor
0.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of
inverter ND rating)
150.0
bA115
Torque limit 4 (Forward regener-
ative), 1st-motor
0.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of
inverter ND rating)
150.0
bA116 -
Torque limit LADSTOP selec-
tion, 1st-motor
00 (Disabled)/01 (Enabled) 00
bA120 -
Over current suppress enable,
1st-motor
00 (Disabled)/01 (Enabled) 01
bA121 -
Over current suppress Level,
1st-motor
(0.0 to 2.0)
× Inverter rated current (A)
*1
*2
bA122 -
Overload restriction 1 mode
selection, 1st-motor
00 (Disabled)/
01 (Accelerate at constant speed)/
02 (Only constant speed)/
03 (Accelerate at constant speed/Increase speed
at regeneration)
01
bA123
Overload restriction 1 active
level, 1st-motor
(0.2 to 2.0)
× Inverter rated current (A)
*1
*3
bA124
Overload restriction 1 action
time, 1st-motor
0.10 to 3600.00 (s) 1.00
bA126 -
Overload restriction 2 mode
selection, 1st-motor
00 (Disabled)/
01 (Accelerate at constant speed)/
02 (Only constant speed)/
03 (Accelerate at constant speed/Increase speed
at regeneration)
01
bA127
Overload restriction 2 active
level, 1st-motor
(0.2 to 2.0)
× Inverter rated current (A)
*1
*3
bA128
Overload restriction 2 Action
time, 1st-motor
0.10 to 3600.00 (s) 1.00