Appendices C Table of Parameters
C - 46
High-function General-purpose Inverter RX2 Series User’s Manual
Code
Codes that
can be
changed
during
operation
Name Data range
Initial
value
Note
Cb-01 ○ Filter time constant of Terminal [Ai1] 1 to 500 (ms) 16
Cb-03 ○ Start value of Terminal [Ai1] 0.00 to 100.00 (%) 0.00
Cb-04 ○ End value of Terminal [Ai1] 0.00 to 100.00 (%) 100.00
Cb-05 ○ Start rate of Terminal [Ai1] 0.0 to [Cb-06] (%) 0.0
Cb-06 ○ End rate of Terminal [Ai1] [Cb-05] to 100.0 (%) 100.0
Cb-07 ○ Start point selection of Terminal [Ai1] 00 (Start amount)/01 (0%) 01
Cb-11 ○ Filter time constant of Terminal [Ai2] 1 to 500 (ms) 16
Cb-13 ○ Start value of Terminal [Ai2] 0.00 to 100.00 (%) 0.00
Cb-14 ○ End value of Terminal [Ai2] 0.00 to 100.00 (%) 100.00
Cb-15 ○ Start rate of Terminal [Ai2] 0.0 to [Cb-16] (%) 20.0
Cb-16 ○ End rate of Terminal [Ai2] [Cb-15] to 100.0 (%) 100.0
Cb-17 ○ Start point selection of Terminal [Ai2] 00 (Start amount)/01 (0%) 01
Cb-21 ○ Filter time constant of Terminal [Ai3] 1 to 500 (ms) 16
Cb-22 - Terminal [Ai3] selection
00 (Single)/
01 (Added to Ai1/Ai2: with reversibility)/
02 (Added to Ai1/Ai2: without reversibility)
00
Cb-23 ○ Start value of Terminal [Ai3] -100.00 to 100.00 (%) -100.00
Cb-24 ○ End value of Terminal [Ai3] -100.00 to 100.00 (%) 100.00
Cb-25 ○ Start rate of Terminal [Ai3] -100.0 to [Cb-26] -100.0
Cb-26 ○ End rate of Terminal [Ai3] [Cb-25] to 100.0 100.0
Cb-30 -
[Ai1] Voltage/Current zero-gain
adjustment
-100.00 to 100.00 0.00
Cb-31 - [Ai1] Voltage/Current gain adjustment 0 to 200.00 100.00
Cb-32 -
[Ai2] Voltage/Current zero-gain
adjustment
-100.00 to 100.00 0.00
Cb-33 - [Ai2] Voltage/Current gain adjustment 0 to 200.00 100.00
Cb-34 -
[Ai3] Voltage/Current zero-gain
adjustment
-100.00 to 100.00 0.00
Cb-35 - [Ai3] Voltage gain adjustment 0 to 200.00 100.00
Cb-40 ○ Thermistor selection
00 (Disabled)/
01 (PTC resistance value enabled)/
02 (NTC resistance value enabled)
00
Cb-41 - Thermistor gain adjustment 0.0 to 1000.0 100.0
Cb-51 to
Cb-57
- Reserved -