C - 47
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-3 Parameter List
C
Code
Codes that
can be
changed
during
operation
Name Data range
Initial
value
Note
CC-01 Output terminal [11] function
See <List of output terminal functions> on page C-49
001
CC-02 Output terminal [12] function 002
CC-03 Output terminal [13] function 003
CC-04 Output terminal [14] function 007
CC-05 Output terminal [15] function 035
CC-06 Output terminal [16] function 000
CC-07 Output terminal [AL] function 017
CC-11 Output terminal [11] function
00 (Normally open)/
01 (Normally closed)
00
CC-12 Output terminal [12] function 00
CC-13 Output terminal [13] function 00
CC-14 Output terminal [14] function 00
CC-15 Output terminal [15] function 00
CC-16 Output terminal [16] function 00
CC-17 Output terminal [AL] function 01
CC-20 Output terminal [11] on-delay time 0.00 to 100.00 (s) 0.00
CC-21 Output terminal [11] off-delay time 0.00 to 100.00 (s) 0.00
CC-22 Output terminal [12] on-delay time 0.00 to 100.00 (s) 0.00
CC-23 Output terminal [12] off-delay time 0.00 to 100.00 (s) 0.00
CC-24 Output terminal [13] on-delay time 0.00 to 100.00 (s) 0.00
CC-25 Output terminal [13] off-delay time 0.00 to 100.00 (s) 0.00
CC-26 Output terminal [14] on-delay time 0.00 to 100.00 (s) 0.00
CC-27 Output terminal [14] off-delay time 0.00 to 100.00 (s) 0.00
CC-28 Output terminal [15] on-delay time 0.00 to 100.00 (s) 0.00
CC-29 Output terminal [15] off-delay time 0.00 to 100.00 (s) 0.00
CC-30 Output terminal [16] on-delay time 0.00 to 100.00 (s) 0.00
CC-31 Output terminal [16] off-delay time 0.00 to 100.00 (s) 0.00
CC-32 Output terminal [AL] on-delay time 0.00 to 100.00 (s) 0.00
CC-33 Output terminal [AL] off-delay time 0.00 to 100.00 (s) 0.00
CC-40
Logical calculation target 1 selection
of LOG1
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-41
Logical calculation target 2 selection
of LOG1
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-42
Logical calculation symbol selection
of LOG1
00 (AND)/01 (OR)/02 (XOR) 00
CC-43
Logical calculation target 1 selection
of LOG2
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-44
Logical calculation target 2 selection
of LOG2
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-45
Logical calculation symbol selection
of LOG2
00 (AND)/01 (OR)/02 (XOR) 00
CC-46
Logical calculation target 1 selection
of LOG3
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-47
Logical calculation target 2 selection
of LOG3
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-48
Logical calculation symbol selection
of LOG3
00 (AND)/01 (OR)/02 (XOR) 00
CC-49
Logical calculation target 1 selection
of LOG4
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-50
Logical calculation target 2 selection
of LOG4
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-51
Logical calculation symbol selection
of LOG4
00 (AND)/01 (OR)/02 (XOR) 00
CC-52
Logical calculation target 1 selection
of LOG5
See <List of output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000
CC-53
Logical calculation target 2 selection
o
f LOG5
See <List of
output terminal functions> on page C-49
062: LOG1 to 068: LOG7 cannnot be selected.
000