C - 59
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-3 Parameter List
C
Hb162 -
Free-V/f frequency 7 setting,
1st-motor
[Hb160] to [Hb104] (Hz) 0.00
Hb163 -
Free-V/f Voltage 7 setting,
1st-motor
0.0 to 1000.0 (V) 0.0
Hb170
Slip Compensation P-gain with
encoder, 1st-motor
0 to 1000 (%) 100
Hb171
Slip Compensation I-gain with
encoder, 1st-motor
0 to 1000 (%) 100
Hb180 Output voltage gain, 1st-motor 0 to 255 (%) 100
Hb202 -
Async.Motor capacity setting,
2nd-motor
0.01 to 160.00 (kW)
*1
Hb203 -
Async.Motor poles setting,
2nd-motor
2 to 48 (poles) 4
Hb204 -
Async.Motor Base frequency
setting, 2nd-motor
10.00 to 590.00 (Hz)
50.00
*2
Hb205 -
Async.Motor Maximum fre-
quency setting, 2nd-motor
10.00 to 590.00 (Hz)
50.00
*2
Hb206 -
Async.Motor rated voltage,
2nd-motor
1 to 1000 (V)
200 V class: 230
400 V class: 400
*2
Hb208 -
Async.Motor rated current,
2nd-motor
0.01 to 10000.00 (A)
*1
Hb210 -
Async.Motor constant R1,
2nd-motor
0.000001 to 1000.000000 (Ω)
*1
Hb212 -
Async.Motor constant R2,
2nd-motor
0.000001 to 1000.000000 (Ω)
*1
Hb214 -
Async.Motor constant L,
2nd-motor
0.000001 to 1000.000000 (mH)
*1
Hb216 -
Async.Motor constant Io,
2nd-motor
0.01 to 10000.00 (A)
*1
Hb218 -
Async.Motor constant J,
2nd-motor
0.00001 to 10000.00000 (kgm
2
)
*1
Hb230 -
Minimum frequency adjust-
ment, 2nd-motor
0.10 to 10.00 (Hz) 0.50
Hb231
Reduced voltage start time set-
ting, 2nd-motor
0 to 2000 (ms) 36
Hb240 -
Manual torque boost opera-
tional mode selection,
2nd-motor
00 (Disabled)/
01 (Always enabled)/
02 (Enabled only for forward revolution)/
03 (Enabled only for reverse revolution)
01
Hb241
Manual torque boost value,
2nd-motor
0.0 to 20.0 (%) 0.0
Hb242
Manual torque boost Peak
speed, 2nd-motor
0.0 to 50.0 (%) 0.0
Hb245 - Eco drive enable, 2nd-motor 00 (Disabled)/01 (Enabled) 00
Hb246
Eco drive response adjustment,
2nd-motor
0.0 to 100.0 (%) 50.0
Hb250 - First free V/f frequency 2 0.00 to [Hb252] (Hz) 0
Hb251 -
Free-V/f Voltage 1 setting,
2nd-motor
0.0 to 1000.0 (V) 0.0
Hb252 -
Free-V/f frequency 2 setting,
2nd-motor
[Hb250] to [Hb254] (Hz) 0.00
Hb253 -
Free-V/f Voltage 2 setting,
2nd-motor
0.0 to 1000.0 (V) 0.0
Hb254 -
Free-V/f frequency 3 setting,
2nd-motor
[Hb252] to [Hb256] (Hz) 0.00
Hb255 -
Free-V/f Voltage 3 setting,
2nd-motor
0.0 to 1000.0 (V) 0.0
Hb256 -
Free-V/f frequency 4 setting,
2nd-motor
[Hb254] to [Hb258] (Hz) 0.00
Code
Codes that
can be
changed
during
operation
Name Data range Initial value Note

Table of Contents