Warning
Number
Warning Name Warning Meaning
A.900 Position Devia-
tion Overflow
This warning occurs if the position deviation
exceeds the specified percentage (Pn520 × Pn51E/
100).
9.4.5 Vibration Detection Level Setting
You can set the vibration detection level (Pn312) to more accurately detect A.520 alarms
(Vibration Alarm) and A.911 warnings (Vibration Warning) when vibration is detected
during machine operation.
Set the initial vibration detection level to an appropriate value. Refer to the following sec-
tion for details.
Ä
Chap. 7.12 ‘Initializing the Vibration Detection Level’ page 246
9.4.6 Setting the Position Deviation Overflow Alarm Level at Servo ON
If the servo is turned ON when there is a large position deviation, the Servomotor will
attempt to return to the original position to bring the position deviation to 0, which may
create a hazardous situation. To prevent this, you can set a position deviation overflow
alarm level at servo ON to restrict operation.
The related parameters and alarms are given in the following tables.
Position Deviation Overflow Alarm Level at Servo ON
Setting
Range
Setting Unit Default Set-
ting
When Ena-
bled
Classifica-
tion
Pn526 1 to
1,073,741,82
3
1 reference
unit
5,242,880 Immediately Setup
(applies to Position Control)
Position Deviation Overflow Warning Level at Servo ON
Setting
Range
Setting Unit Default Set-
ting
When Ena-
bled
Classifica-
tion
Pn528 10 to 100 1% 100 Immediately Setup
(applies to Position Control)
Speed Limit Level at Servo ON
Setting
Range
Setting Unit Default Set-
ting
When Ena-
bled
Classifica-
tion
Pn529 0 to 10,000
1 min
-1
10,000 Immediately Setup
(applies to Position Control)
Related Warnings
Related Parameters
Rotary Servomotors
Sigma-7 Series SERVOPACKs
Tuning
Precautions to Ensure Safe Tuning > Setting the Position Deviation Overflow Alarm Level at Servo ON