SERVOPACK model Space on
Right Side
Cooling Fan Installation
Conditions
10 mm above SERVO-
PACK’s Top Surface
SGD7S- R70A, R90A, 1R6A, 2R8A,
3R8A, 5R5A, 7R6A, R70F,
R90F, 2R1F, 2R8F
1 mm min. Air speed: 1.0 m/s min.
120A, 180A, 200A, 330A,
470A, 550A, 590A, 780A
10 mm min. Air speed: 1.0 m/s min.
4.6 Monitoring the Installation Environment
You can use the SERVOPACK Installation Environment Monitor parameter to check the
operating conditions of the SERVOPACK in the installation environment.
You can check the SERVOPACK installation environment monitor with either of the fol-
lowing methods.
n Using the SigmaWin+: Life Monitor - Installation Environment Monitor - SERVO-
PACK
n Panel Operator or Digital Operator: Un025 (Installation Environment Monitor [%])
Implement one or more of the following actions if the monitor value exceeds 100%.
n Lower the surrounding temperature.
n Decrease the load.
The value of the SERVOPACK Installation Environment Monitor param-
eter will increase by about 10% for each 10°C increase in the ambient
temperature.
Always observe the surrounding air temperature given in the SERVO-
PACK environment conditions. Even if the monitor value is 100% or
lower, you cannot use a SERVOPACK in a location that exceeds the
specified surrounding air temperature.
Sigma-7 Series SERVOPACKs
SERVOPACK Installation
Monitoring the Installation Environment
| | PROFINET Communications - SIEP YEUOC7P 02A Revision 0 | en | 80