The Eb0h, Eb2h to Eb9h, and EC0h to EC2h alarms can occur when a
Safety Module is connected. Refer to the following manual for details.
&
AC Servo Drive Σ-V-Series/Σ-V-Series for Large-Capacity Models/Σ-7-
Series User’s Manual Safety Module (Manual No.: SIEP C720829 06)
16.4.3 Troubleshooting Alarms
16.4.3.1 Overview
The causes of and corrections for the alarms are given in the following tables. Contact
your YASKAWA representative if you cannot solve a problem with the correction given in
the tables.
16.4.3.2 Troubleshooting of the PROFINET Module Alarms
Alarm Code Alarm Name Possible Cause Confirmation Correction
A.A12
(1A12h)
Abnormal Com-
munication
Transition
IO-Controller in STOP mode during
PROFIdrive state "S4: Operation".
Check the cause why
the IO-Controller
changed to STOP
mode.
Change IO-Controller
to RUN mode and send
command fault
acknowledge.
PROFINET communication link
down during PROFIdrive state "S4:
Operation" as a results of cable or
wiring disconnection.
Check the PROFINET
cable and connector
wiring.
Correct the wiring and
send command fault
acknowledge.
Application Relation (AR) with the
IO-Controller is aborted during
PROFIdrive state "S4: Operation"
(e.g. IO-Controller closed the con-
nection, etc.).
Check possible rea-
sons for Application
Relation (AR) abort.
Re-establish connec-
tion with IO-Controller
and send command
fault acknowledge.
A.A20
(1A20h)
Parameter Set-
ting Error
The parameter settings are out of
range during power-on.
Check the parameter
settings. Verify that the
non-volatile parameter
values do not exceed
the current Motor Max.
values.
"Initialize the parameter
settings (load device
parameter set (PNU
976)) and cycle power."
Correct the parameter
settings and store them
non-volatile (transfer in
non-volatile memory
(PNU 977)).
Check the wiring of the
encoder.
Turn power supply
OFF, correct the
encoder connection
and turn power supply
ON.
A.A40
(1A40h)
System Initiali-
zation Error
The system initialization at power-
on sequence failed.
- Replace the
PROFINET SERVO-
PACK module.
A.A41
(1A41h)
Communica-
tions Device Ini-
tialization Error
A failure occurred in the PROFINET
SERVOPACK module.
- Replace the
PROFINET SERVO-
PACK module.
A.A42
(1A42h)
System Run-
time Error
The flash load/store execution
failed.
- Cycle power.
Sigma-7 Series SERVOPACKs
Maintenance
Alarm Displays > Troubleshooting Alarms
| | PROFINET Communications - SIEP YEUOC7P 02A Revision 0 | en | 594