4.5 Mounting Interval
4.5.1 Installing One SERVOPACK in a Control Panel
Provide the following spaces around the SERVOPACK.
30 mm min.
30 mm min.
40 mm min.
*
40 mm min.
SERVOPACK
Fig. 36: Mounting Spaces around the SERVOPACK
* For this dimension, ignore items protruding from the main body of the SERVOPACK.
4.5.2 Installing More Than One SERVOPACK in a Control Panel
Provide the following intervals between the SERVOPACKs and spaces around the SER-
VOPACKs.
Install cooling fans above the SERVOPACKs so that hot spots do not
occur around the SERVOPACKs. Provide sufficient intervals and spaces
as shown in the following figure to enable cooling by the fans and natural
convection.
Fan
30 mm min.
This distance depends
on the model.
30 mm min.
Fan
40 mm min.
40 mm min.
SERVOPACK
SERVOPACK
SERVOPACK
SERVOPACK
Fig. 37: Mounting Spaces around the SERVOPACK when Installing More Than One SER-
VOPACK in a Control Panel
The space required on the right side of a SERVOPACK (when looking at the SERVO-
PACK from the front) depends on the SERVOPACK models. Refer to the following table.
Sigma-7 Series SERVOPACKs
SERVOPACK Installation
Mounting Interval > Installing More Than One SERVOPACK in a Control Panel
| | PROFINET Communications - SIEP YEUOC7P 02A Revision 0 | en | 79