4.7 Derating Specifications
If you use the SERVOPACK at a surrounding air temperature of 55°C to 60°C or at an
altitude of 1,000 m to 2,000 m, you must apply the derating rates given in the following
graphs.
Effective torque
Surrounding air temperature
Altitude
Surrounding air temperature and altitude
Effective torque
Effective torque
100%
60%
2000 m
100%
1000 m
80%
0%
0%
0 m
2000 m
1000 m0 m
100%
0%
48%
-5°C 55°C 60°C -5°C 55°C 60°C
Fig. 38: Derating SGD7S-R70A, -R90A, -1R6A, -2R8A, -R70F, -R90F, -2R1F, and -2R8F
80%
2000 m
1000 m
0 m
2000 m
1000 m
0 m
-5°C 55°C 60°C -5°C 55°C 60°C
Surrounding air temperature Altitude Surrounding air temperature and altitude
100%
100% 100%
0% 0% 0%
Effective torque
Effective torque
Effective torque
Fig. 39: Derating SGD7S-3R8A, -5R5A, -7R6A, -120A, -180A, -200A, -330A, -470A,
-550A, -590A, and -780A
4.8 EMC Installation Conditions
This section gives the installation conditions that were used for EMC certification testing.
The EMC installation conditions that are given here are the conditions that were used to
pass testing criteria at Yaskawa. The EMC level may change under other conditions, such
as the actual installation structure and wiring conditions. These Yaskawa products are
designed to be built into equipment. Therefore, you must implement EMC measures and
confirm compliance for the final equipment.
The applicable standards are EN 55011 group 1 class A, EN 61000-6-2, EN 61000-6-4,
and EN 61800-3 (category C2, second environment).
SGD7S-R70A, -R90A,
-1R6A, -2R8A, -R70F, -
R90F, -2R1F, and -2R8F
SGD7S-3R8A, -5R5A,
-7R6A, -120A, -180A,
-200A, -330A, -470A,
-550A, -590A, and -780A
Sigma-7 Series SERVOPACKs
SERVOPACK Installation
EMC Installation Conditions