The following utility functions execute the Servo ON command (Enable Operation com-
mand).
Utility Function No. Function Name
Fn002 Jog
Fn003 Origin Search
Fn004 Jog Program
Fn00E Autotune Motor Current Detection Signal Offset
Fn080 Polarity Detection
Fn201 Advanced Autotuning without Reference
Fn206 Easy FFT
If any of the above utility functions was executed, the utility function must
be ended. Perform the operation to return to the Main Menu for the utility
functions on the Digital Operator. Refer to the following manual for oper-
ating procedures.
&
Σ-7-Series Digital Operator Operating Manual (Manual No.: SIEP
S800001 33)
1. Specify Shutdown in controlword (6040h, bits 0 to 3) to reset the Servo Drive.
2. Specify Switch ON and the Servo ON command (Enable Operation command) in
controlword (6040h, bits 0 to 3).
Power will be supplied to the motor.
12.3.6 Detecting Errors in HWBB Signal
If only the /HWBB1 or the /HWBB2 signal is input, an A.Eb1 alarm (Safety Function
Signal Input Timing Error) will occur unless the other signal is input within 10 seconds.
This makes it possible to detect failures, such as disconnection of an HWBB signal.
CAUTION!
The A.Eb1 alarm (Safety Function Signal Input Timing Error) is not a
safety-related element. Keep this in mind when you design the system.
12.3.7 HWBB Input Signal Specifications
If an HWBB is requested by turning OFF the two HWBB input signal channels (/HWBB1
and /HWBB2), the power supply to the Servomotor will be turned OFF within 8 ms.
Recovery Procedure
Sigma-7 Series SERVOPACKs
Safety Functions
Hard Wire Base Block (HWBB and SBB) > HWBB Input Signal Specifications