3.
Click the Import Button or click and Button to manually adjust the set fre-
quency.
When you click the Import Button, the residual vibration frequency in the Servo-
motor is read as the set frequency. (The frequency can be read only when the
residual vibration frequency is between 1.0 and 100.0.)
Frequency detection will not be performed if there is no vibration or
if the vibration frequency is outside the range of detectable frequen-
cies. If a vibration frequency is not detected, provide a means of
measuring the vibration frequency.
Fig. 276: Vibration Suppression AXIS#00 - Manual Adjustment of the Frequency
Sigma-7 Series SERVOPACKs
Tuning
Vibration Suppression > Operating Procedure