4 s
5 s max.
When displaying a warning is specified:
Pn008 = n.ooo1
When displaying an alarm is specified:
Pn008 = n.ooo0
ALM
OFF
Alarm
ON
Battery voltage
monitored
Battery voltage monitored
Control power supply
Normal status
Fig. 375: Battery Alarm_Warning Selection
n When Installing a Battery on the Host Controller
1. Turn ON only the control power supply to the SERVOPACK.
2. Remove the old battery and mount a new battery.
3. Turn OFF the control power supply to the SERVOPACK to clear the A.830 alarm
(Absolute Encoder Battery Error).
4. Turn ON the control power supply to the SERVOPACK again.
5. Make sure that the alarm has been cleared and that the SERVOPACK operates
normally.
n When Using an Encoder Cable with a Battery Case
1. Turn ON only the control power supply to the SERVOPACK.
If you remove the battery or disconnect the Encoder Cable while
the control power supply to the SERVOPACK is OFF, the absolute
encoder data will be lost.
2. Open the cover of the Battery Case.
Fig. 376: Encoder Cable with a Battery Case - Open the Cover
Battery Replacement Pro-
cedure
Sigma-7 Series SERVOPACKs
Maintenance
Inspections and Part Replacement > Replacing the Battery