Alarm Code Alarm Name Possible Cause Confirmation Correction Reference
A.042
(1042h)
Parameter
Combination
Error
The speed of program
jogging went below
the setting range
when Pn533 or Pn585
(Program Jogging
Speed) was changed.
Check to see if the
detection condi-
tions
*1
are satisfied.
Increase the setting
of Pn533 or Pn585.
Ä
Chap. 8.7
‘Convenient
Function to Use
during Trial
Operation’
page 276
A.044
(1044h)
Semi-Closed/
Fully-Closed
Loop Control
Parameter Set-
ting Error
The setting of the
Fully-closed Module
does not match the
setting of Pn002 =
n.X (External
Encoder Usage).
Check the setting of
Pn002 = n.X.
Make sure that the
setting of the Fully-
closed Module
agrees with the set-
ting of Pn002 =
n.X.
Ä
Chap. 11.4.3
‘Setting the
Motor Direction
and the
Machine Move-
ment Direction’
page 458
A.050
(1050h)
Combination
Error (The
capacities of the
SERVOPACK
and Servomotor
do not match.)
The SERVOPACK
and Servomotor
capacities do not
match each other.
Confirm that the fol-
lowing condition is
met: 1/4 ≤ (Servo-
motor capacity/
SERVOPACK
capacity) ≤ 4
Select a proper com-
bination of the SER-
VOPACK and Servo-
motor capacities.
Ä
Chap. 2.7
‘Combinations
of SERVO-
PACKs and Ser-
vomotors’
page 48
A failure occurred in
the encoder.
Replace the encoder
and check to see if
the alarm still occurs.
Replace the Servo-
motor or encoder.
A failure occurred in
the SERVOPACK.
The SERVOPACK
may be faulty.
Replace the SERVO-
PACK.
A.051
(1051h)
Unsupported
Device Alarm
The motor parameter
file was not written to
the linear encoder.
(This applies only
when not using a
Serial Converter Unit.)
Check to see if the
motor parameter file
was written to the
linear encoder.
Write the motor
parameter file to the
linear encoder.
Ä
Chap. 6.7
‘Writing Linear
Servomotor
Parameters’
page 148
An unsupported Serial
Converter Unit or
encoder (e.g., an
external encoder) is
connected to the
SERVOPACK.
Check the product
combination specifi-
cations.
Change to a correct
combination of
models.
A.070
(1070h)
Motor Type
Change
Detected (The
connected
motor is a dif-
ferent type of
motor from the
previously con-
nected motor.)
A Rotary Servomotor
was removed and a
Linear Servomotor
was connected.
Set the parameters
for a Linear Servo-
motor and reset the
motor type alarm.
Then, turn the power
supply to the SER-
VOPACK OFF and
ON again.
Ä
Chap. 16.4.8
‘Resetting Motor
Type Alarms’
page 636
A Linear Servomotor
was removed and a
Rotary Servomotor
was connected.
Set the parameters
for a Rotary Servo-
motor and reset the
motor type alarm.
Then, turn the power
supply to the SER-
VOPACK OFF and
ON again.
Ä
Chap. 16.4.8
‘Resetting Motor
Type Alarms’
page 636