Supported Rack Requirements
Shelf
Supported
Installation Features
19-inch 23-inch
ETSI 300-
mm
Depth
ETSI 600-
mm
Depth
SH12
(cables
w/MPO
connectors)
Two-post cabinet Supported Supported Supported Supported
Four-post cabinet Supported
1
Supported
1
Supported
1
Supported
1
Cabinet depth ≥400 mm
2
≥300 mm 300 mm 600 mm
Back-to-back
cabinets
Supported Supported Supported N/A
Air holes present in
cabinet front/back
l <500 mm depth –
Required
l >500 mm depth –
Cabinet door may
be metal or glass, if
enough air flow
volume bottom to
top in cabinet
l 12 in. depth –
Required
l ≥20 in. depth –
Cabinet door may
be metal or glass, if
enough air flow
volume bottom to
top in cabinet
Required Not
required
SH12
(cables
w/LC
connectors)
Two-post cabinet Supported Supported Supported Supported
Four-post cabinet Supported
1
Supported
1
Supported
1
Supported
1
Cabinet depth ≥400 mm
2
≥300 mm 300 mm 600 mm
Back-to-back
cabinets
N/A N/A Supported N/A
Air holes present in
cabinet front/back
l 300 mm depth –
Required
l ≥500 mm depth –
Cabinet door may
be metal or glass, if
enough air flow
volume bottom to
top in cabinet
l 12 in. depth –
Required
l ≥20 in. depth –
Cabinet door may
be metal or glass, if
enough air flow
volume bottom to
top in cabinet
Required Not
required
SH4R
(cables
w/MPO
connectors)
Two-post cabinet Not supported Not supported Not
supported
Not
supported
Four-post cabinet Supported Supported Not
supported
Not
supported
Cabinet depth 600 to 1000 mm 600 to 1000 mm Not
supported
Not
supported
Air holes present in
cabinet front/back
l 600 mm depth –
Required
l ≥800 mm depth –
Cabinet door may
be metal or glass, if
enough air flow
volume bottom to
top in cabinet
l 600 mm depth –
Required
l ≥800 mm depth –
Cabinet door may
be metal or glass, if
enough air flow
volume bottom to
top in cabinet
Not
supported
Not
supported
Table 62: Cabinet Installations