Description of device parameters Proline Promag 300 Modbus RS485
210 Endress+Hauser
Additional information Description
The desired simulation value is defined in the Pulse value parameter (→  210).
Selection
Off
Simulation of the double pulse output is switched off. The device is in normal measuring
mode or another process variable is being simulated.
Fixed value
Pulses are continuously output with the pulse width specified in the Pulse width
parameter (→  147).
Down-count. val.
The pulses specified in the Pulse value parameter (→  210) are output.
Pulse value
Navigation  Expert → Diagnostics → Simulation → Pulse value (0989)
Prerequisite In the Puls.outp.sim. parameter (→  209), the Down-count. val. option is selected.
Description Use this function to enter a pulse value for simulation of the double pulse output. In this
way, users can verify the correct adjustment of the double pulse output and the correct
function of downstream switching units.
User entry 0 to 65 535
Dev. alarm sim.
Navigation  Expert → Diagnostics → Simulation → Dev. alarm sim. (0654)
Description Use this function to switch the device alarm on and off.
Selection Off
On
Factory setting Off
Additional information Description
The display alternates between the measured value and a diagnostic message of the
"Function check" category (C) while simulation is in progress.