Parameter List
11
11.20 Defaults by Drive Model and Duty Rating ND/HD
SIEPCYEUOQ2V01A Q2V Technical Manual 411
No.
*1
Name Unit Default
- Drive Model - 2008 2010 2012 2018
C6-01
ND/HD Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive KVA
Selection
Hex. 64 65 66 67
E2-11
(E4-11, E5-
02)
Motor Rated
Power (kW)
kW 1.1 1.5 1.5 2.2 2.2 3.0 3.0 3.7
L2-04
Powloss
Ramp
Time@recov
ery
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
UV Detection
Lvl (Uv1)
- 190 190 190 190 190 190 190 190
L3-02
StallP
Level@Accel
% 150 120 150 120 150 120 150 120
L3-06
StallP
Level@Run
% 150 120 150 120 150 120 150 120
L3-24
Acc@Rated
Torque
s 0.142 0.166 0.166 0.145 0.145 0.145 0.145 0.154
L8-02
Overheat Alm
Level
°C 110 110 110 110 110 110 115 115
L8-09
Ground Fault
Selection
- 0 0 0 0 0 0 0 0
n1-03
HuntPrev
Time Constant
ms 10 10 10 10 10 10 10 10
n3-02
HSB CurrLim
Level
1 150 120 150 120 150 120 150 120
n5-02
Mot Inertia
Acceleration
Time
s 0.142 0.166 0.166 0.145 0.145 0.145 0.145 0.154
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 2021 2030 2042 2056
C6-01
ND/HD Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive KVA
Selection
Hex. 68 6A 6B 6D
E2-11
(E4-11, E5-
02)
Motor Rated
Power (kW)
kW 3.7 5.5 5.5 7.5 7.5 11 11 15
b3-04
SpSrch V/F
Gain
% 100 100 100 100 100 100 100 100
b3-06
Speed Curr
Lev1 for
Estimation
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed ACR
PGain for
Estimation
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Dir. Determ.
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
eSave Filter
Time
s 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-04
eSave Coef.
Value
- 122.9 94.75 94.75 72.69 72.69 70.44 70.44 63.13
C6-02
Carrier
Frequency
Selection
- 3 7 3 7 3 7 3 7
E2-01
(E4-01)
Mot Rated
Current (FLA)
A 14 19.6 19.6 26.6 26.6 39.7 39.7 53
E2-02
(E4-02)
Mot Rated
Slip
Hz 2.73 1.5 1.5 1.3 1.3 1.7 1.7 1.6
E2-03
(E4-03)
Mot No-Load
Current
A 4.5 5.1 5.1 8 8 11.2 11.2 15.2