Parameter Details
12
12.7 H: TERMINALS
SIEPCYEUOQ2V01A Q2V Technical Manual 601
Figure 12.85 Frequency Detection 2 Time Chart
■ 15: FreqDetect 3
Setting Value Function Description
15 FreqDetect 3
The terminal deactivates when the output frequency is higher than the value of “L4-03 [SpAgree Det.Level(+/-)] + L4-04
[SpAgree Det.Width(+/-)]”. After the terminal deactivates, the terminal stays deactivated until the output frequency is at the
value of L4-03.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is less than the value of L4-03 or it is not more than the value of L4-03
+ L4-04.
OFF : The output frequency is higher than the value of L4-03 + L4-04.
Figure 12.86 Example of Frequency Detection 3 (value of L4-03 Is Positive)
Note:
Figure 12.86 shows the result of the configuration when L4-07 = 2 [SpAgree Det.Selection = Always Detect]. The default setting of L4-
07 is 1 [No Detect@BB]. When the speed agreement detection selection is “No Detection during Baseblock”, the terminal is deactivated
when the drive output stops.
■ 16: FreqDetect 4
Setting Value Function Description
16 FreqDetect 3
The terminal activates when the output frequency is higher than the value of L4-03 [SpAgree Det.Level(+/-)]. After the terminal
activates, the terminal stays activated until the output frequency is at the value of L4-03 - L4-04.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is higher than the value of L4-03.
OFF : The output frequency is less than the value of “L4-03 - L4-04,” or it is not more than the
value of L4-03.