3.3 Main Circuit Wiring
64 SIEPCYEUOQ2V01A Q2V Technical Manual
Model Terminal
Recommended
Gauge
mm
2
Applicable Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening Torque
N∙m (in∙lb)
Size Shape
B012
L/L1, N/L2 5.5 3.5 - 8 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 2 2 - 3.5 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1 5.5 3.5 - 8 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2 2 - 3.5 10 M4
1.5 - 1.7
(13.5 - 15)
3.5
*2
2 - 5.5
*2
- M4
1.2 - 1.5
(10.6 - 13.3)
B018
L/L1, N/L2 8 3.5 - 14 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 3.5 2 - 5.5 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1 8 3.5 - 14 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2 2 - 3.5 10 M4
1.5 - 1.7
(13.5 - 15)
5.5
*2
4 - 8
*2
- M5
2.0 - 2.5
(17.7 - 22.1)
*1 Remove the insulation from the wire ends to the length shown in “Wire Stripping Length”.
*2 If you turn on the built-in EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
Three-Phase 400 V Class (UL-compliance)
Model Terminal
Recommended
Gauge
mm
2
Applicable Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening Torque
N∙m (in∙lb)
Size Shape
4001
R/L1, S/L2, T/L3 2 2 - 3.5 8 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 2 2 - 3.5 8 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2 2 2 - 3.5 8 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 2 2 - 3.5 8 M3
0.5 - 0.6
(4.4 - 5.3)
2
*2
2 - 5.5
*2
- M4
1.2 - 1.5
(10.6 - 13.3)
4002
R/L1, S/L2, T/L3 2 2 - 3.5 8 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 2 2 - 3.5 8 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2 2 2 - 3.5 8 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 2 2 - 3.5 8 M3
0.5 - 0.6
(4.4 - 5.3)
2
*2
2 - 5.5
*2
- M4
1.2 - 1.5
(10.6 - 13.3)